HOUSE BILL NO. 507

AMENDMENT IN THE NATURE OF A SUBSTITUTE

Offered January 14, 2026

Prefiled January 12, 2026

A BILL to amend the Code of Virginia by adding in Article 1 of Chapter 13 of Title 10.1 a section numbered 10.1-1322.6, relating to data center carbon dioxide-emitting backup generators; air monitoring.

—————

Patrons—McAuliff, Simonds, Singh and Thomas

—————

(ProposedReferred by the Houseto Committee on Agriculture, Chesapeake and Natural Resources

on ________________)

(Patron Prior to Substitute—Delegate McAuliff)

A BILL to amend the Code of Virginia by adding in Article 1 of Chapter 13 of Title 10.1 a section numbered 10.1-1322.6, relating to permit requirements for data centers; emission limits for certain engine-generator sets.

—————

Be it enacted by the General Assembly of Virginia:

1. That the Code of Virginia is amended by adding in Article 1 of Chapter 13 of Title 10.1 a section numbered 10.1-1322.6 as follows:

§ 10.1-1322.6. PermitsData forcenter databackup centersgenerators ; emissionair limits for certain engine -generator set smonitoring .

A. As used in this section:

"Data center" means the same as that term is defined in subdivision A 43 of § 58.1-3506 .

"Diesel oxidation catalyst" means a flow - through exhaust device that contains a honeycomb structure covered with a layer of chemical catalyst contain ing small amounts of precious metal such as platinum or palladium that interact with and oxidize pollutants , including carbon monoxide and unburned hydrocarbons , in the exhaust stream , there by reducing carbon monoxide emissions.

"Diesel particulate filter" means an emission control technology that reduces particulate matter emissions by trapping the particles in a flow filter substrate and periodically removes the collected particles by either physical action or by oxidizing or burning off the particles in a process called regeneration.

" Engine-generator set" or "gen-set" means the combination of an electrical generator and an engine mounted together to form a single piece of equipment.

"Selective catalytic reduction" means a control device that reduces the exhaust gas concentration of nitrogen oxides by injecting an ammonia solution or urea into the exhaust gas stream, which in the presence of a catalyst, reacts with the nitrogen oxides to form nitrogen gas and water vapor.

"Tier 4 equivalent" means a gen-set with a selective catalytic reduction system or equivalent for nitrogen oxides control, a diesel oxidation catalyst system or equivalent for carbon monoxide control, and a diesel particulate filter or equivalent for particulate matter control.

B. For any application submitted for a data center on or after July 1, 2026 , for a permit issued by the D epartment pursuant to this chapter, including coverage under any general permit, the D epartment shall not issue such permit unless the emission limit for each gen-set established by such permit is equal to or less than the emissions achieved by a Tier 4 equivalent gen-set.

C. Nothing in this section shall be construed to prevent the Department from (i) determining th e Best Available Control Technology, Lowest Achievable Emission Rate, Reasonably Available Control Technology, any New Source Performance Standard, or any National Emission Standards for Hazardous Air Pollutants or (ii) establishing in a permit issued by the D epartment pursuant to this chapter more stringent emission limits than those achieved by a Tier 4 equivalent gen-set .

A. A data center shall only use a carbon dioxide-emitting backup generator in an emergency . During such an emergency, such backup generator used shall meet or exceed the U.S. Environmental Protection Agency's (i) Tier 4 emissions standards or (ii) Tier 2 emissions standards and be equipped with a selective catalytic reduction system. In no case shall a carbon dioxide-emitting backup generator be used in excess of 500 hours per year.

B. Beginning July 1 , 202 7 , a data center shall utilize energy storage as its primary backup power source for a minimum of two hours in an emergency and shall only use carbon dioxide-emitting backup generators during grid emergencies after such energy storage resource is depleted, provided that such generators meet or exceed the U.S. Environmental Protection Agency's (i) Tier 4 e missions standards or (ii) Tier 2 emissions standards and are equipped with selective catalytic reduction systems.

C. The Department shall notify all property owners living within one - quarter mile of a data center operating carbon dioxide-emitting backup generators conti nuously for more than four hours as soon as is practicable after the Department has been notified that such backup generators will be in operation .

D. The Department shall require data center operators to utilize monitoring devices to maintain records of emissions, pollutants, and fuel data and operating parame ters as necessary to demonstrate compliance with applicable permits and report the results of such monitoring to the Department on a monthly basis. The Department shall make each such report available to the public on its website.

E. The Department shall establish and maintain an air quality monitoring site or sites in any locality or other political subdivision of the Commonwealth with 100 or more us e able carbon dioxide-emitting backup generators. Such sites shall be located within one-quarter mile of any cluster of such backup generators . F or the purposes of this subsection, "cluster" means a group of 25 or more carbon dioxide-emitting backup generators.

F. The Department, in collaboration with the Department of Health, shall monitor and assess the cumulativ e impacts of data center carbon dioxide -emitting backup generators on human health in jurisdictions where there are at least 100 such backup generators. Should the cumulative impacts of emissions and pollutants from such backup generators exceed U.S. Environmental Protection Agency or Virginia standards for air quality, the Department and the Department of Health shall take all measures available to support the reduction of such backup generator emissions and pollut ants .

G. When a permit application is made for a new or modi fied emissions sourc e that is expected to emit any hazardous air pollutants or toxic air contaminants and the release point for such pollutants or contaminants is located within 3,000 feet of an infant or early childhood daycare, pre school, elementary school, or secondary school , the Department shall notify such schools of such application and make such notice available to the general public .

H. The Board may promulgate regulations as it deems necessary to effectuate the provisions of this section.

Volver al texto completo