PRINTER'S NO. 4117 THE GENERAL ASSEMBLY OF PENNSYLVANIAHOUSE BILL No.2888 Session of 2026 INTRODUCED BY WEBSTER, HANBIDGE, PIELLI, HILL-EVANS, RIVERA, WAXMAN, HOWARD, SHUSTERMAN, KHAN, OTTEN AND HADDOCK, NOVEMBER 4, 2026 REFERRED TO COMMITTEE ON ENERGY, NOVEMBER 4, 2026 AN ACTEstablishing reporting and information submission requirements for hyperscale computer data centers operating in this Commonwealth; providing for alternative compliance payments, for energy plans, for water plans, for regional benefits plans, for ratepayer protections, for community benefit plans and agreements, for municipal comments, for confidentiality, for records, for lists of tenants, for enforcement, for regulations and guidelines and for municipal zoning; imposing duties on the Department of Environmental Protection, the Department of Community and Economic Development and the Pennsylvania Public Utility Commission; and imposing penalties.The General Assembly of the Commonwealth of Pennsylvania hereby enacts as follows:Section 1. Short title.This act shall be known and may be cited as the Data Center Community Support and Compliance Act.Section 2. Definitions.The following words and phrases when used in this act shall have the meanings given to them in this section unless the context clearly indicates otherwise:"Alternative compliance payment." A payment calculated at 12345678910111213141516171819202122
the alternative compliance payment rate and made to PEDA by an owner or operator under section 3(g) for a shortfall in the amount of incremental clean firm energy required under section 3(a)(5)(v)(B)(I), (II) or (III)."Alternative compliance payment rate." A rate expressed in dollars per megawatt-hour that the Department of Environmental Protection determines annually by doubling the estimated average levelized cost of electricity from solar photovoltaic technology as published by the United States Energy Information Administration in the Annual Energy Outlook."Average Statewide wage." The Statewide annual average wage calculated by the Department of Labor and Industry from wage data reported by employers covered under the act of December 5, 1936 (2nd Sp.Sess., 1937 P.L.2897, No.1), known as the Unemployment Compensation Law."Clean firm energy." Energy derived from nuclear energy, hydroelectric power, including pumped storage, geothermal energy, fuel cells, solar energy, including solar energy paired with storage resources, wind energy, including wind energy paired with storage resources, clean hydrogen-fueled energy generation, battery energy storage systems or long-duration storage resources if the energy resource meets all of the following requirements:(1) The energy resource is dispatchable or capable of providing firm service so that the energy resource can deliver electricity on demand with an availability factor consistent with standards established by the commission.(2) The energy resource constitutes incremental capacity as a result of any of the following:(i) The placement of a new energy resource that 20260HB2888PN4117 - 2 - 123456789101112131415161718192021222324252627282930
generates clean firm energy in service on or after January 1, 2025.(ii) The completion on or after January 1, 2025, of an uprate or efficiency improvement at an existing energy resource that generates clean firm energy, if the uprate or efficiency improvement increased the accredited capacity or net output of the energy resource.(iii) The placement of a battery energy storage system in service on or after January 1, 2025, that provides at least two hours of continuous discharge or another duration that the commission determines provides reliable capacity value.(iv) The placement of a long-duration storage resource in service on or after January 1, 2025, that provides at least four hours of continuous discharge capability and firm service as determined by the commission."Clean firm energy generation." Electricity generated from clean firm energy. The term includes electricity generated from solar energy paired with a storage resource or wind energy paired with a storage resource. The term does not include electricity discharged from a battery energy storage system or long-duration storage resource."Clean hydrogen-fueled energy generation." The generation of electricity using hydrogen produced through a process with a life cycle greenhouse gas emissions rate of less than four kilograms of carbon dioxide equivalent per kilogram of hydrogen."Commission." The Pennsylvania Public Utility Commission."Common parent." The most senior corporation that owns or controls a unitary business that includes an owner or operator.20260HB2888PN4117 - 3 - 123456789101112131415161718192021222324252627282930
"Community benefit agreement." A written agreement between an owner or operator and the host municipality that addresses the subjects under section 6(c)."Community benefit plan." A written plan prepared by an owner or operator under section 6."Electric distribution company." As defined in 66 Pa.C.S. § 2803 (relating to definitions)."Environmental justice community." A geographic area characterized by increased pollution burden and vulnerable populations based on demographic, economic, health and environmental data and duly identified by the Department of Environmental Protection."Facility." One or more parcels of land located in this Commonwealth, together with any structure and personal property located on the land."Host municipality." A city, borough, incorporated town, township or home rule municipality, other than a county, in which a hyperscale computer data center is located."Hyperscale computer data center." A facility of a retail electric customer that meets all of the following requirements:(1) The facility is used primarily or exclusively for electronic information services, including the management, storage, processing and dissemination of electronic data and information through computer systems, servers, networking equipment and related components.(2) The facility satisfies the applicable minimum monthly maximum demand threshold in accordance with all of the following:(i) The applicable minimum threshold is:(A) twenty megawatts if the peak load of the 20260HB2888PN4117 - 4 - 123456789101112131415161718192021222324252627282930
electric distribution company serving the facility is 2,500 megawatts or more; or(B) one megawatt if the peak load of the electric distribution company serving the facility is less than 2,500 megawatts.(ii) In determining whether the facility satisfies the applicable minimum threshold under subparagraph (i), the aggregate monthly maximum demand shall include all of the following:(A) The monthly maximum demand attributable to each company that is affiliated with or under common ownership with the retail electric customer.(B) The combined monthly maximum demand of multiple facilities at a single location if the monthly maximum demand of each facility is below the applicable minimum threshold but the combined monthly maximum demand of the facilities equals or exceeds the applicable minimum threshold."Hyperscale computer data center equipment." Equipment or software located on the same parcel of land as a hyperscale computer data center that is used to outfit, operate or support a hyperscale computer data center. The term includes component parts, installations, refurbishments, replacements and upgrades to the equipment or software, regardless of whether the equipment or software is affixed to or incorporated into real property, including any of the following:(1) Equipment necessary for the transformation, generation, distribution or management of electricity required to operate computer servers or similar data storage equipment, including battery energy storage devices, 20260HB2888PN4117 - 5 - 123456789101112131415161718192021222324252627282930
uninterruptible energy supplies, conduit, gaseous fuel piping, cabling, duct banks, switches, switchboards, batteries and testing equipment.(2) Equipment necessary to cool and maintain a controlled environment for the operation of computer servers or data storage systems and other components of the hyperscale computer data center, including mechanical equipment, refrigerant piping, gaseous fuel piping, adiabatic and free cooling systems, cooling towers, water softeners, air handling units, indoor direct exchange units, fans, ducting and filters.(3) Water conservation systems, including facilities or mechanisms designed to collect, conserve and reuse water.(4) Software, including enabling software and licensing agreements.(5) Computer servers or similar data storage equipment, chassis, networking equipment, switches, racks, cabling, trays and conduits.(6) Monitoring equipment and security systems.(7) Modular data centers and preassembled components of an item described in this definition, including components used in the manufacturing of modular data centers.(8) Other tangible personal property that is essential to the operations of a hyperscale computer data center."Incremental capacity." Additional capacity or additional net energy output from an energy resource. For purposes of this definition, the commission shall determine the amount of additional capacity or additional net energy output based on the unforced capacity value assigned to the energy resource under the applicable PJM capacity accreditation rules and verify and 20260HB2888PN4117 - 6 - 123456789101112131415161718192021222324252627282930
certify that the additional accredited capacity or additional net energy output would not have been available to the bulk electric system in this Commonwealth without an investment described under any of the following:(1) The placement in service of a new energy resource on or after January 1, 2025.(2) An uprate or efficiency improvement completed on or after January 1, 2025, at an existing resource that provides clean firm energy generation or an existing long-duration storage resource, to the extent that the improvement increases accredited capacity or net output available to the electric grid.(3) For a battery energy storage system or long-duration storage resource, the installation of new storage equipment or the expansion or repowering of an existing storage resource completed on or after January 1, 2025, that increases discharge duration, rated capacity or firm service capability."Locational deliverability area." A geographic area within the PJM region that has limited transmission capability to import capacity to satisfy the reliability requirement of the area as specified in Schedule 10.1 of the PJM Reliability Assurance Agreement."New investment." Construction, expansion or build out of space at a new or existing hyperscale computer data center on or after the effective date of this definition and the purchase and installation of hyperscale computer data center equipment. The term does not include an item described under paragraph (4) or (5) of the definition of "hyperscale computer data center equipment."20260HB2888PN4117 - 7 - 123456789101112131415161718192021222324252627282930
"Owner or operator." An entity, multiple entities or affiliated entities that own or operate a hyperscale computer data center."PEDA." The Pennsylvania Energy Development Authority."Pennsylvania climate change connectivity." A geographic area identified by the Pennsylvania Game Commission Wildlife Action Plan Conservation Opportunity Area Tool as important for wildlife habitat connectivity."PJM Interconnection, L.L.C." or "PJM." The regional transmission organization approved by the Federal Energy Regulatory Commission to coordinate wholesale electricity markets and transmission operations within a geographic region that includes this Commonwealth."Qualified third-party entity." An entity that the Department of Community and Economic Development determines has the professional expertise necessary to verify information required under section 5 and that has no ownership interest in and is not affiliated with the owner or operator of, or a tenant of, the hyperscale computer data center for which a report is filed under section 5."Regional benefits plan." A written plan prepared by an owner or operator under section 3(b)(5)."Retail electric customer." As defined in 66 Pa.C.S. § 2803."Solar ready." Designed and constructed to allow solar photovoltaic panels to be installed on at least 40% of the roof area, including preinstalled conduit and sufficient space for inverters and other necessary equipment."Tenant." An entity that contracts with the owner or operator of a hyperscale computer data center to use or occupy part of the hyperscale computer data center.20260HB2888PN4117 - 8 - 123456789101112131415161718192021222324252627282930
"Tier four equivalent." A combination of an electrical generator and an engine mounted together to form a single piece of equipment that includes the following:(1) A selective catalytic reduction system or equivalent for nitrogen oxide control.(2) A diesel oxidation catalyst system or equivalent for carbon monoxide control.(3) A diesel particulate filter or equivalent for particulate matter control."Unitary business." A single economic enterprise consisting of separate parts of a single business entity or a commonly controlled group of business entities that are sufficiently interdependent, integrated and interrelated through their activities to provide a synergy and mutual benefit that produces a sharing or exchange of value among the parts and a significant flow of value to the separate parts.Section 3. Information submitted to departments.(a) Department of Environmental Protection.--Except as provided under subsection (c), within one year after the effective date of this subsection, the owner or operator of a hyperscale computer data center shall submit to the Department of Environmental Protection all of the following information on a form developed by the Department of Environmental Protection:(1) The name, address and telephone number of the owner or operator.(2) The address of the site where the hyperscale computer data center is or will be located, including, if applicable, information sufficient to identify the portion of a facility comprising the hyperscale computer data center.(3) The name of the common parent of a unitary business 20260HB2888PN4117 - 9 - 123456789101112131415161718192021222324252627282930
that meets any of the following:(i) The unitary business is responsible for the permanent management and operation of the hyperscale computer data center.(ii) The unitary business uses at least 50% of the capacity of the hyperscale computer data center.(4) The size of each building in square feet and the acreage of the campus.(5) An energy plan that includes all of the following:(i) The expected energy generation or storage resource that will be colocated with the hyperscale computer data center, if any.(ii) The expected percentage of electricity that will be used from nonemitting sources and an explanation of how the electricity will be procured.(iii) The expected average annual power usage effectiveness.(iv) The expected reuse of heat at a connected or colocated facility.(v) A plan to build, bring or buy incremental capacity that includes all of the following:(A) Incremental capacity sufficient to meet the full electricity demand of the hyperscale computer data center. The incremental capacity must be located within the same locational deliverability area as the hyperscale computer data center or, if the incremental capacity is not located within the same locational deliverability area, the plan must include documentation demonstrating that electricity from the new generation or storage resource is deliverable to 20260HB2888PN4117 - 10 - 123456789101112131415161718192021222324252627282930
the hyperscale computer data center and incremental to existing supply through a contract, interconnection agreement or other verifiable means consistent with PJM requirements and applicable utility tariffs.(B) A plan to satisfy the following annual incremental clean firm energy procurement requirements using resources located within this Commonwealth:(I) For calendar years 2027 through 2029, not less than 10% of the annual electricity consumption of the hyperscale computer data center.(II) For calendar years 2030 through 2034, not less than 14.5% of the annual electricity consumption of the hyperscale computer data center.(III) For calendar year 2035 and each calendar year thereafter, not less than 32% of the annual electricity consumption of the hyperscale computer data center.(IV) For each calendar year in which the hyperscale computer data center procures less incremental clean firm energy than the amount required under subclause (I), (II) or (III), the owner or operator shall make an alternative compliance payment to PEDA for the procurement shortfall in accordance with subsection (g).(vi) A commitment to pay, through an applicable base rate, surcharge or other ratemaking mechanism, costs 20260HB2888PN4117 - 11 - 123456789101112131415161718192021222324252627282930
caused in whole or in part by the interconnection, service or load of the hyperscale computer data center, including costs associated with emergency ancillary services, transmission, distribution, network upgrades or dedicated facilities, if the costs are directly attributable to the provision of electric service to the hyperscale computer data center or would not have been incurred but for the electricity demand of the hyperscale computer data center. The owner or operator may demonstrate compliance with this subparagraph by submitting a copy of the electric service agreement for the hyperscale computer data center showing that the owner or operator purchases electricity from an electric distribution company under an electric service tariff that contains terms that:(A) are no less stringent than the terms of the final Large Load Customer Model Tariff adopted by the commission at Docket No. M-2025-3054271; and(B) address the contribution of the hyperscale computer data center to embedded system costs.(vii) A commitment to submit all applicable filings to the commission and comply with commission regulations governing commercial data centers.(viii) For a hyperscale computer data center with a floor area exceeding 100,000 square feet, a commitment to design and construct the facility in a solar ready manner that facilitates and optimizes the installation of solar photovoltaic panels on unoccupied roof areas or other areas of the building.(6) A water plan that includes all of the following:20260HB2888PN4117 - 12 - 123456789101112131415161718192021222324252627282930
(i) Anticipated water discharges, including treated water discharges, if any.(ii) Estimated average annual water consumption.(iii) Anticipated maximum daily water demand.(iv) The source of water to be used, including the water quality standard use designation of the source under 25 Pa. Code Ch. 93 (relating to water quality standards), if any.(v) Expected average annual water usage effectiveness.(vi) A commitment to use the best available technologies and other efficiency measures to mitigate impacts on the quantity or quality of water for other uses or users, including designated and existing uses under 25 Pa. Code Ch. 93.(vii) A hydrogeological study that meets all of the following requirements:(A) The owner or operator shall submit the study if any part of the physical footprint, any point of water withdrawal or any point source of storm water discharge of the hyperscale computer data center is located in any of the following areas:(I) A watershed designated as high quality waters under 25 Pa. Code Ch. 93.(II) The watershed of a source of a public water system regulated under 25 Pa. Code Ch. 109 (relating to safe drinking water).(III) An area within 1,000 feet of a tributary that flows into a source of a public water system regulated under 25 Pa. Code Ch. 109.20260HB2888PN4117 - 13 - 123456789101112131415161718192021222324252627282930
(B) The study shall include all of the following:(I) An assessment of baseline water quality at all relevant tributary monitoring points.(II) An assessment of the effect of anticipated consumptive use and storm water discharge on surface water and groundwater sources.(III) Identification of specific mitigation measures to protect water sources.(C) A professional geologist who is licensed in this Commonwealth and has relevant experience in hydrogeological analysis shall prepare the study.(viii) If the hyperscale computer data center is within the jurisdiction of a river basin commission, documentation that the owner or operator has received approval for the water withdrawal from the river basin commission.(ix) For a hyperscale computer data center described under subparagraph (vii), if construction and ground disturbance have not commenced before the effective date of this subparagraph, a commitment to perform baseline water quality monitoring, as approved by the Department of Environmental Protection, at the applicable tributary monitoring points identified in the hydrogeological study before construction or ground disturbance commences. Beginning with the first full calendar year after the hyperscale computer data center commences commercial operations or the effective date of this subparagraph, whichever is later, the owner or operator shall include 20260HB2888PN4117 - 14 - 123456789101112131415161718192021222324252627282930
annual water quality monitoring data from the approved tributary monitoring points in the report required under section 4. After reviewing the annual water quality monitoring data, the Department of Environmental Protection may require the owner or operator to take corrective action if the data identify material degradation of a water source at an applicable tributary monitoring point.(7) A sustainability plan that includes the following:(i) The owner or operator plans to deploy the best available technology to limit water and energy consumption by the hyperscale computer data center by obtaining certification under a recognized performance-based facility standard system or systems applicable to hyperscale computer data centers addressing energy and water use as adopted by the Department of Environmental Protection.(ii) A commitment to minimize local air pollutants by:(A) Utilizing a backup energy system that relies on zero-emission energy generation or storage or backup generators with emissions equal to or less than the emissions achieved by a tier four or tier four equivalent generator.(B) Implementing operational practices such as reduced generator runtime and limits on backup generation utilization to emergency use and limited testing and maintenance consistent with Federal and State air quality laws and regulations.(C) Utilizing at least three air quality 20260HB2888PN4117 - 15 - 123456789101112131415161718192021222324252627282930
monitors that continuously record air quality at the site.(D) Creating a detailed plan for recordkeeping of the air quality and making the records available to government or private entities upon request.(iii) For a hyperscale computer data center located in an area identified as Pennsylvania climate change connectivity:(A) explaining defined measures to minimize and ameliorate impacts to wildlife habitat or offset net loss of habitat and ecological function; and(B) making good faith efforts to fund and collaborate with private conservation and public resource entities to support the monitoring of impacts to land, water and biological resources.(iv) For a hyperscale computer data center located in an environmental justice community:(A) explaining defined measures to offset any increased environmental exposures or net environmental effects; and(B) making good faith efforts to fund and collaborate with municipal, civic and private industries to positively impact the population characteristics of the environmental justice community. The good faith efforts may incorporate the commitments and plans required for the application.(b) Department of Community and Economic Development.--Except as provided under subsection (c), within one year after the effective date of this subsection, the owner or operator of a hyperscale computer data center shall submit to the Department 20260HB2888PN4117 - 16 - 123456789101112131415161718192021222324252627282930
of Community and Economic Development all of the following information on a form developed by the Department of Community and Economic Development:(1) The name, address and telephone number of the owner or operator.(2) The address of the site where the hyperscale computer data center is or will be located, including, if applicable, information sufficient to identify the portion of a facility comprising the hyperscale computer data center.(3) The name of the common parent of a unitary business that meets any of the following:(i) The unitary business is responsible for the permanent management and operation of the hyperscale computer data center.(ii) The unitary business uses at least 50% of the capacity of the hyperscale computer data center.(4) The size of each building in square feet and the acreage of the campus.(5) A regional benefits plan that includes a commitment to take all of the following actions:(i) Identify a regional impact area that includes all of the following:(A) Each municipality located within a 25-mile radius of the hyperscale computer data center.(B) Each county located within a 25-mile radius of the hyperscale computer data center.(C) Any school district, emergency service provider or water, sewer or transportation authority located within a 25-mile radius of the hyperscale computer data center whose infrastructure or service 20260HB2888PN4117 - 17 - 123456789101112131415161718192021222324252627282930
area is reasonably expected to be affected by the hyperscale computer data center.(ii) Provide documentation that the owner or operator will deliver written notice to each political subdivision and authority identified under subparagraph (i) and offer at least one informational meeting to each entity to receive comments on anticipated regional impacts.(iii) Summarize the expected regional impacts, including traffic, emergency services, water and wastewater use, storm water, air quality and noise, based on each applicable study prepared in connection with the community benefit agreement under section 6.(iv) Describe the specific mitigation actions that the owner or operator will take to address the regional impacts identified under subparagraph (iii). The mitigation actions may include any of the following:(A) Transportation improvements located outside the host municipality.(B) Support for county-level emergency management planning.(C) Regional air quality monitoring or environmental restoration.(D) Watershed or storm water improvements.(E) Other commitments identified during consultation with regional authorities.(v) Provide financial contributions to support a project or service that produces a measurable benefit within the regional impact area. A contribution may be made directly to an affected municipality, school 20260HB2888PN4117 - 18 - 123456789101112131415161718192021222324252627282930
district, emergency service provider or public authority.(6) A noise and vibration mitigation plan that includes the following:(i) Documentation that the hyperscale computer data center is in compliance with an applicable local ordinance or regulation relating to sound or vibration limits, including a required permit, study or certification demonstrating compliance.(ii) If the jurisdiction where the hyperscale computer data center is located does not have an applicable zoning ordinance relating to noise or vibration standards, a description of the mitigation measures that the owner or operator will take to mitigate noise and vibration impacts on the surrounding community. The description shall include any of the following designed to minimize noise impacts:(A) operational practices;(B) engineering controls; or(C) monitoring activities.(c) Submission before construction.--The owner or operator of a hyperscale computer data center for which construction begins on or after the effective date of this subsection shall submit the information required under subsections (a) and (b) before construction begins. For purposes of this subsection, a facility shall be deemed a hyperscale computer data center if the owner or operator reasonably expects the facility, when operational, to satisfy the applicable minimum monthly maximum demand threshold under the definition of "hyperscale computer data center" in section 2.(d) Department construction certifications.--No later than 20260HB2888PN4117 - 19 - 123456789101112131415161718192021222324252627282930
90 days after receiving the information required under subsections (a) and (b) and section 6, the Department of Environmental Protection shall review the energy plan provided under subsection (a)(5) and the water plan provided under subsection (a)(6), and the Department of Community and Economic Development shall review the regional benefits plan required under subsection (b)(5) and the community benefit plan under section 6 for a hyperscale computer data center that the commencement of construction takes place on or after the effective date of this subsection. If the Department of Environmental Protection and Department of Community and Economic Development determine that the plans are provided in compliance with the requirements of this act, they shall issue a written certification indicating the compliance to the hyperscale computer data center owner or operator. If the Department of Environmental Protection or Department of Community and Economic Development determines plans are not in compliance with the requirements of this act, the department that determined the noncompliance shall issue a written denial to the owner or operator. A hyperscale computer data center for which the commencement of construction takes place on or after the effective date of this subsection must receive a certification from both the Department of Environmental Protection and the Department of Community and Economic Development under this paragraph prior to the commencement of construction of the data center.(e) Department operations certifications.--Prior to the commencement of commercial operations of a hyperscale computer data center for which commercial operations begin on or after the effective date of this subsection, the hyperscale computer 20260HB2888PN4117 - 20 - 123456789101112131415161718192021222324252627282930
data center must receive a written certification in a form and manner determined by the respective department as follows:(1) Certification from the Department of Environmental Protection that the water and energy plans certified under subsection (d) have been implemented in accordance with the requirements of this act.(2) Certification from the Department of Community and Economic Development that the regional benefits plan and community benefit plan certified under subsection (d) have been implemented in accordance with the requirements of this act.(3) Certification from the Department of Environmental Protection that the ratepayer protection certification submitted under subsection (f) was submitted in accordance with the requirements of this act.(4) Certification from the Department of Community and Economic Development that the community benefit agreement required under section 6 has been developed in accordance with the requirements of this act.(f) Ratepayer protections.--(1) Before a hyperscale computer data center commences commercial operations on or after the effective date of this section, the owner or operator shall submit to the Department of Environmental Protection, on a form and in a manner established by the department, a certification that any change made to the energy plan required under subsection (a)(5) has not imposed additional costs on other customers of the electric distribution company.(2) The owner or operator of a hyperscale computer data center that commenced commercial operations before the 20260HB2888PN4117 - 21 - 123456789101112131415161718192021222324252627282930
effective date of this section shall submit the certification required under paragraph (1) within one year after submitting the information required under subsections (a) and (b).(g) Alternative compliance payment.--(1) The Department of Environmental Protection shall annually determine the alternative compliance payment rate and publish the rate on the department's publicly accessible Internet website.(2) The amount of an alternative compliance payment shall equal the alternative compliance payment rate for the applicable calendar year multiplied by the number of megawatt-hours by which the incremental clean firm energy procured by the hyperscale computer data center is less than the amount required under subsection (a)(5)(v)(B)(I), (II) or (III), as applicable.(3) The owner or operator shall pay the alternative compliance payment to PEDA in the manner and by the deadline established by the Department of Environmental Protection.(h) Commission duties.--The commission shall establish standards for determining availability factors and firm service under the definition of "clean firm energy" and procedures for verifying and certifying incremental capacity under the definition of "incremental capacity" in section 2.Section 4. Annual report to Department of Environmental Protection.(a) Filing.--Beginning with the first full calendar year after the effective date of this subsection, the owner or operator of a hyperscale computer data center operating in this Commonwealth shall file an annual report with the department on a form and in a manner required by the department.20260HB2888PN4117 - 22 - 123456789101112131415161718192021222324252627282930
(b) Contents.--The annual report shall include all of the following:(1) The amount and source of water used by the hyperscale computer data center during the reporting year.(2) A certification by the owner or operator that the hyperscale computer data center's water use has not adversely impacted the quantity or quality of water for another use or user, including designated and existing uses under 25 Pa. Code Ch. 93 (relating to water quality standards).(3) The amount of electricity used by the hyperscale computer data center during the reporting year.(4) If applicable, the annual water quality monitoring data required under section 3(a)(6)(ix)(B).(5) Other information required by the department to implement the provisions of this act administered by the department.(c) Definition.--As used in this section, the term "department" means the Department of Environmental Protection of the Commonwealth.Section 5. Annual report to Department of Community and Economic Development.(a) Filing.--Beginning with the first full calendar year after the effective date of this subsection, the owner or operator of a hyperscale computer data center operating in this Commonwealth shall file an annual report with the department on a form and in a manner required by the department.(b) Verification.--The owner or operator shall have a qualified third-party entity verify the annual report required under subsection (a).(c) Contents.--The annual report shall include all of the 20260HB2888PN4117 - 23 - 123456789101112131415161718192021222324252627282930
following:(1) For a hyperscale computer data center subject to section 6, a certification signed by an officer of the owner or operator that identifies whether the owner or operator completed each commitment contained in the community benefit plan required under section 6 during the reporting year and, if not, identifies each commitment that remains in progress and the steps that the owner or operator is taking to complete the commitment.(2) Other information required by the department to implement the provisions of this act administered by the department.(d) Public posting.--The department shall post the information submitted under subsection (c)(1) on its publicly accessible Internet website. The department shall withhold information from public disclosure in accordance with section 9.(e) Municipal comments.--A municipality in which a hyperscale computer data center is located or a municipal authority created under 53 Pa.C.S. Ch. 56 (relating to municipal authorities) that provides service within 25 miles of a hyperscale computer data center may submit written comments to the department if the municipality or authority has reason to believe that the owner or operator is not satisfying one or more commitments contained in a community benefit plan or community benefit agreement. The department shall review the comments and may request additional information from the owner or operator to evaluate compliance.(f) Definition.--As used in this section, the term "department" means the Department of Community and Economic Development of the Commonwealth.20260HB2888PN4117 - 24 - 123456789101112131415161718192021222324252627282930
Section 6. Community benefit plan and agreement.(a) Plan required.--An owner or operator of a hyperscale computer data center subject to this section under section 13(b) shall submit a community benefit plan to the Department of Community and Economic Development and the host municipality before the hyperscale computer data center begins operation, expands or makes new investment.(b) Contents.--The community benefit plan shall include a commitment to take all of the following actions:(1) Make at least $250,000,000 of cumulative new investment in the hyperscale computer data center.(2) Create at least 200 jobs during the construction phase of development, each paying the applicable prevailing minimum wage and benefit rates as determined for each applicable craft or classification by the Department of Labor and Industry under the act of August 15, 1961 (P.L.987, No.442), known as the Pennsylvania Prevailing Wage Act.(3) On or before the fourth anniversary of the establishment of the community benefit plan, create at least 50 new full-time jobs, each paying at least 125% of the average Statewide wage.(4) For each year after the fourth anniversary of the establishment of the community benefit plan, pay aggregate annual compensation of at least $1,500,000 to full-time employees employed at the hyperscale computer data center.(5) Prepare a hiring plan for recruiting and training local workers, including local workforce participation in site preparation and site construction, using registered apprenticeship programs and skilled construction labor.(c) Community benefit agreement.--The owner or operator 20260HB2888PN4117 - 25 - 123456789101112131415161718192021222324252627282930
shall engage in good faith discussions with the host municipality to develop a community benefit agreement that addresses all of the following:(1) Details about planned development phases.(2) Noise, vibration and lighting study requirements and mitigation techniques.(3) A traffic study.(4) Air quality protection requirements consistent with Federal law and the laws of this Commonwealth.(5) A plan for addressing aesthetic concerns, including landscaping or visual buffers.(6) An emergency management plan that addresses training, coordination and reasonable resource needs of the emergency management professionals and first responders responsible for the host municipality.(7) Financial contributions toward local priorities.(8) Annual reporting to the host municipality addressing progress under the community benefit agreement.(9) Other items determined by the host municipality.Section 7. Records.(a) Maintenance.--An owner or operator and a tenant shall maintain detailed records relating to a report, community benefit plan or community benefit agreement under this act, including records of new investment, costs of buildings, costs of hyperscale computer data center equipment, purchase journals and information, certifications and documentation submitted under section 3.(b) Inspection.--An owner or operator and a tenant shall make the records required under subsection (a) available for inspection as follows:20260HB2888PN4117 - 26 - 123456789101112131415161718192021222324252627282930
(1) Upon request of the Department of Environmental Protection, information, certifications and documentation submitted to the Department of Environmental Protection under section 3(a) and records pertaining to a report under section 4 shall be made available to authorized personnel of the Department of Environmental Protection.(2) Upon request of the Department of Community and Economic Development, information, certifications and documentation submitted to the Department of Community and Economic Development under section 3(b) and records pertaining to a report under section 5 or a community benefit plan or community benefit agreement under section 6 shall be made available to authorized personnel of the Department of Community and Economic Development.(c) Retention.--An owner or operator and a tenant shall retain the records required under subsection (a) as follows:(1) Records pertaining to a report under section 4 or information, certifications and documentation submitted to the Department of Environmental Protection under section 3(a) shall be retained for the period that the Department of Environmental Protection determines necessary to administer the provisions of this act administered by the Department of Environmental Protection.(2) Records pertaining to a report under section 5, a community benefit plan or community benefit agreement under section 6 or information and documentation submitted to the Department of Community and Economic Development under section 3(b) shall be retained for the period that the Department of Community and Economic Development determines necessary to administer the provisions of this act that are 20260HB2888PN4117 - 27 - 123456789101112131415161718192021222324252627282930
administered by the Department of Community and Economic Development.Section 8. List of tenants.(a) Department of Environmental Protection.--An owner or operator of a hyperscale computer data center shall annually provide the Department of Environmental Protection with a list of tenants. To the extent permitted under Federal law, the owner or operator shall also provide the Department of Environmental Protection with a list of tenants upon request by the department. The Department of Environmental Protection shall treat information that it receives under this subsection in accordance with section 9.(b) Department of Community and Economic Development.--An owner or operator of a hyperscale computer data center shall annually provide the Department of Community and Economic Development with a list of tenants. To the extent permitted under Federal law, the owner or operator shall also provide the Department of Community and Economic Development with a list of tenants upon request by the department. The Department of Community and Economic Development shall treat information that it receives under this subsection in accordance with section 9.Section 9. Confidential information.(a) Public records.--Except as provided under subsection (b), information contained in a report required under section 4 or 5 and information submitted under section 3(a) or (b) shall be public.(b) Request to withhold.--A person submitting information to the Department of Environmental Protection or the Department of Community and Economic Development under this act may request, at the time the information is submitted, that the department 20260HB2888PN4117 - 28 - 123456789101112131415161718192021222324252627282930
receiving the information withhold any of the following from public disclosure:(1) A trade secret or confidential proprietary information, as those terms are defined in section 102 of the act of February 14, 2008 (P.L.6, No.3), known as the Right-to-Know Law.(2) Information exempt from access under section 708(b)(3) of the Right-to-Know Law.(c) Department determination.--The Department of Environmental Protection and the Department of Community and Economic Development shall each determine whether to withhold information that it receives under this act in accordance with subsection (b) and the Right-to-Know Law.Section 10. Enforcement.(a) Audit.--The Department of Environmental Protection and the Department of Community and Economic Development may conduct audits as follows:(1) The Department of Environmental Protection may audit information, a certification or documentation submitted to the Department of Environmental Protection under section 3(a), a report or certification required under section 4 or a record required under section 7 that relates to information, a certification, documentation or a report under section 3(a) or 4.(2) The Department of Community and Economic Development may audit information or documentation submitted to the Department of Community and Economic Development under section 3(b), a report or certification required under section 5, a community benefit plan or community benefit agreement under section 6 or a record required under section 20260HB2888PN4117 - 29 - 123456789101112131415161718192021222324252627282930
7 that relates to a report or certification under section 5, a community benefit plan or community benefit agreement under section 6 or information or documentation under section 3(b).(b) Notice.--(1) If the Department of Environmental Protection determines that a person failed to comply with a provision of this act administered by the Department of Environmental Protection, the Department of Environmental Protection may issue a written notice of noncompliance to the person. The notice shall identify the basis for the determination and the action required to cure the noncompliance.(2) If the Department of Community and Economic Development determines that a person failed to comply with a provision of this act administered by the Department of Community and Economic Development, the Department of Community and Economic Development may issue a written notice of noncompliance to the person. The notice shall identify the basis for the determination and the action required to cure the noncompliance.(c) Cure period.--(1) A person that receives a notice from the Department of Environmental Protection under subsection (b)(1) shall have 60 days from the date of the notice to cure the noncompliance or submit a corrective action plan to the Department of Environmental Protection.(2) A person that receives a notice from the Department of Community and Economic Development under subsection (b)(2) shall have 60 days from the date of the notice to cure the noncompliance or submit a corrective action plan to the Department of Community and Economic Development.20260HB2888PN4117 - 30 - 123456789101112131415161718192021222324252627282930
(d) Civil penalty.--(1) The Department of Environmental Protection may impose a civil penalty of not more than $10,000 for each violation if a person fails to cure the noncompliance or submit a corrective action plan under subsection (c)(1) for the first seven days after the conclusion of the cure period for which a violation is not cured. If the violation has not been cured for more than seven days after the end of the cure period, the maximum civil penalty per violation shall be $25,000 per violation beginning on the eighth day after the end of the cure period and for each day thereafter until the violation is cured. If the violation identified in the notice under subsection (b)(1) consists of the submission of inaccurate, false or materially misleading information in a report or other material required to be submitted to the department under this act and the person fails to cure the noncompliance or submit a corrective action plan under subsection (c)(1), the Department of Environmental Protection may impose, in lieu of the civil penalty of not more than $10,000, a civil penalty of not more than $25,000 for each violation for the first seven days after the conclusion of the cure period for which a violation is not cured. If the violation has not been cured for more than seven days after the end of the cure period, the maximum civil penalty shall be $50,000 per violation beginning on the eighth day after the end of the cure period and for each day thereafter until the violation is cured.(2) The Department of Community and Economic Development may impose a civil penalty of not more than $10,000 for each violation if a person fails to cure the noncompliance or 20260HB2888PN4117 - 31 - 123456789101112131415161718192021222324252627282930
submit a corrective action plan under subsection (c)(2) for the first seven days after the conclusion of the cure period for which a violation is not cured. If the violation has not been cured for more than seven days after the end of the cure period, the maximum civil penalty shall be $25,000 per violation beginning on the eighth day after the end of the cure period and for each day thereafter until the violation is cured. If the violation identified in the notice under subsection (b)(2) consists of the submission of inaccurate, false or materially misleading information in a report or other material required to be submitted to the department under this act and the person fails to cure the noncompliance or submit a corrective action plan under subsection (c)(2), the Department of Community and Economic Development may impose, in lieu of the civil penalty of not more than $10,000, a civil penalty of not more than $25,000 for each violation for the first seven days after the conclusion of the cure period for which a violation is not cured. If the violation has not been cured for more than seven days after the end of the cure period, the maximum civil penalty shall be $50,000 per violation beginning on the eighth day after the end of the cure period and for each day thereafter until the violation is cured.(e) Continuing violation.--(1) Each day that a violation identified in a notice under subsection (b)(1) continues after the expiration of the cure period under subsection (c)(1) may constitute a separate violation.(2) Each day that a violation identified in a notice under subsection (b)(2) continues after the expiration of the 20260HB2888PN4117 - 32 - 123456789101112131415161718192021222324252627282930
cure period under subsection (c)(2) may constitute a separate violation.(f) Deposit.--A civil penalty imposed and collected under this section by the Department of Environmental Protection or the Department of Community and Economic Development shall be deposited into the General Fund.(g) Collection.--If a person fails to pay a civil penalty imposed under this section by the Department of Environmental Protection or the Department of Community and Economic Development, the department that imposed the civil penalty may refer the matter to the Attorney General. The Attorney General shall recover the amount by action in the appropriate court.Section 11. Regulations, guidelines and implementation.(a) Regulations.--(1) The Department of Environmental Protection and the Department of Community and Economic Development may each promulgate regulations necessary to implement the provisions of this act administered by each department.(2) The commission may promulgate regulations necessary to implement the provisions of this act administered by the commission.(b) Temporary regulations.--(1) In order to facilitate the prompt implementation of this act, the Department of Environmental Protection and the Department of Community and Economic Development may each promulgate temporary regulations necessary to implement the provisions of this act administered by that department during the two years following the effective date of this paragraph. Temporary regulations promulgated under this paragraph shall expire no later than three years following the effective date 20260HB2888PN4117 - 33 - 123456789101112131415161718192021222324252627282930
of this paragraph or upon promulgation of final regulations, whichever occurs first.(2) Temporary regulations promulgated under paragraph (1) shall not be subject to any of the following:(i) Section 612 of the act of April 9, 1929 (P.L.177, No.175), known as The Administrative Code of 1929.(ii) Sections 201, 202, 203, 204 and 205 of the act of July 31, 1968 (P.L.769, No.240), referred to as the Commonwealth Documents Law.(iii) Sections 204(b) and 301(10) of the act of October 15, 1980 (P.L.950, No.164), known as the Commonwealth Attorneys Act.(iv) The act of June 25, 1982 (P.L.633, No.181), known as the Regulatory Review Act.(3) Regulations promulgated after the two-year period under paragraph (1) shall be promulgated as provided by law.(c) Guidelines and forms.--The Department of Environmental Protection and the Department of Community and Economic Development shall each develop and publish written guidelines and forms necessary to implement the provisions of this act administered by that department. Each department shall publish its guidelines on its publicly accessible Internet website.(d) Consultation.--The Department of Environmental Protection and the Department of Community and Economic Development may consult with the Department of Labor and Industry, the Pennsylvania Emergency Management Agency, the Pennsylvania Public Utility Commission, PEDA, PJM and other agencies and offices as necessary to implement this act.Section 12. Municipal zoning.20260HB2888PN4117 - 34 - 123456789101112131415161718192021222324252627282930
Nothing in this act shall affect the zoning authority of a municipality.Section 13. Applicability.(a) Annual reports.--Sections 3, 4 and 5 shall apply to each hyperscale computer data center operating in this Commonwealth.(b) Community benefit plan.--Section 6 shall apply to a hyperscale computer data center that begins operation, expands or makes new investment on or after the effective date of this subsection.Section 14. Effective date.This act shall take effect in 60 days.20260HB2888PN4117 - 35 - 1234567891011