| By: Miles | S.B. No. 1368 | |
| A BILL TO BE ENTITLED | |
| AN ACT | |
| relating to an emergency preparedness and contingency operations | |
| plan, including temperature regulation, for nursing facility and | |
| assisted living facility residents during an emergency; providing | |
| penalties. | |
| BE IT ENACTED BY THE LEGISLATURE OF THE STATE OF TEXAS: | |
| SECTION 1. Subchapter K, Chapter 242, Health and Safety | |
| Code, is amended by adding Section 242.405 to read as follows: | |
| Sec. 242.405. EMERGENCY PREPAREDNESS AND CONTINGENCY | |
| OPERATIONS PLAN; TEMPERATURE REGULATION. (a) In this section: | |
| (1) "Area of refuge" means a climate-controlled area | |
| of a nursing facility that is designated for use during a power | |
| outage or other emergency to provide safety, care, and other | |
| resources to residents. | |
| (2) "Bedfast resident" means a resident who is unable | |
| to transfer out of bed and unable to turn and position themselves in | |
| bed. | |
| (b) A nursing facility shall adopt and implement an | |
| emergency preparedness and contingency operations plan that | |
| requires the facility to provide in an emergency: | |
| (1) for each resident other than a bedfast resident, a | |
| climate-controlled area of refuge with at least 15 square feet per | |
| resident; | |
| (2) for each bedfast resident, a climate-controlled | |
| room; and | |
| (3) notice to the commission of an unplanned | |
| interruption or loss for more than 12 hours of electric utility | |
| service. | |
| (c) An emergency preparedness and contingency operations | |
| plan adopted in accordance with this section must require a nursing | |
| facility to maintain a temperature between 68 and 82 degrees | |
| Fahrenheit for: | |
| (1) each area of refuge designated for facility | |
| residents; and | |
| (2) each climate-controlled room for bedfast | |
| residents. | |
| (d) The executive commissioner shall adopt rules to enforce | |
| this section. | |
| (e) A nursing facility shall submit the emergency | |
| preparedness and contingency operations plan required by this | |
| section to the commission in the form and manner prescribed by the | |
| commission. | |
| (f) A nursing facility shall include in the emergency | |
| preparedness and contingency operations plan adopted in accordance | |
| with this section its policies and information on: | |
| (1) building equipment, including the location of and | |
| type of on-site generator equipment or backup power source; and | |
| (2) residents, including residents who are bedfast and | |
| residents who are dependent on electrically powered equipment. | |
| (g) The commission shall assess a penalty in accordance with | |
| Subchapter C against a nursing facility found in violation of this | |
| section. | |
| SECTION 2. Subchapter D, Chapter 247, Health and Safety | |
| Code, is amended by adding Section 247.073 to read as follows: | |
| Sec. 247.073. EMERGENCY PREPAREDNESS AND CONTINGENCY | |
| OPERATIONS PLAN; TEMPERATURE REGULATION. (a) In this section: | |
| (1) "Area of refuge" means a climate-controlled area | |
| in an assisted living facility that is designated for use during a | |
| power outage or other emergency to provide safety, care, and other | |
| resources to residents. | |
| (2) "Bedfast resident" means an assisted living | |
| facility resident who is unable to transfer out of bed and unable to | |
| turn and position themselves in bed. | |
| (b) An assisted living facility shall adopt and implement an | |
| emergency preparedness and contingency operations plan that | |
| requires the facility to provide in an emergency: | |
| (1) for each assisted living facility resident other | |
| than a bedfast resident, a climate-controlled area of refuge with | |
| at least 15 square feet per resident; | |
| (2) for each bedfast assisted living facility | |
| resident, a climate-controlled room; and | |
| (3) notice to the commission of an unplanned | |
| interruption or loss for more than 12 hours of electric utility | |
| service. | |
| (c) An emergency preparedness and contingency operations | |
| plan adopted in accordance with this section must require an | |
| assisted living facility to maintain a temperature between 68 and | |
| 82 degrees Fahrenheit for: | |
| (1) each area of refuge designated for assisted living | |
| facility residents; and | |
| (2) each climate-controlled room for bedfast assisted | |
| living facility residents. | |
| (d) The executive commissioner shall adopt rules to enforce | |
| this section. | |
| (e) The commission shall establish construction and | |
| licensure standards for assisted living facilities constructed | |
| after September 1, 2026, including standards for: | |
| (1) the integration of backup power systems or a | |
| connection point for a backup power system; and | |
| (2) the evacuation of assisted living facility | |
| residents in emergencies to other buildings on the same premises. | |
| (f) An assisted living facility shall submit the emergency | |
| preparedness and contingency operations plan required by this | |
| section to the commission in the form and manner prescribed by the | |
| commission. | |
| (g) An assisted living facility shall include in the | |
| emergency preparedness and contingency operations plan adopted in | |
| accordance with this section its policies and information on: | |
| (1) building equipment, including the location of and | |
| type of on-site generator equipment or backup power source; and | |
| (2) assisted living facility residents, including | |
| residents who are bedfast and residents who are dependent on | |
| electrically powered equipment. | |
| (h) The commission shall assess a penalty in accordance with | |
| Subchapter C against an assisted living facility found in violation | |
| of this section. | |
| SECTION 3. (a) Not later than January 1, 2026: | |
| (1) each nursing facility shall adopt and implement an | |
| emergency preparedness and contingency operations plan as required | |
| by Section 242.405, Health and Safety Code, as added by this Act; | |
| and | |
| (2) each assisted living facility shall adopt and | |
| implement an emergency preparedness and contingency operations | |
| plan as required by Section 247.073, Health and Safety Code, as | |
| added by this Act. | |
| (b) Notwithstanding Sections 242.405 and 247.073, Health | |
| and Safety Code, as added by this Act, a nursing facility or | |
| assisted living facility is not subject to assessment of a penalty | |
| for a violation of those sections until on or after January 1, 2027. | |
| SECTION 4. This Act takes effect September 1, 2025. |