Introduced
Underlined text would be added to current law. Struck-through text would be removed.
| By: Troxclair | H.B. No. 5569 |
| A BILL TO BE ENTITLED | |
| AN ACT | |
| relating to fire safety standards and emergency operations plans | |
| for the operation of battery energy storage. | |
| BE IT ENACTED BY THE LEGISLATURE OF THE STATE OF TEXAS: | |
| SECTION 1. Subtitle B, Title 4, Utilities Code, is amended | |
| by adding Chapter 187 to read as follows: | |
| CHAPTER 187. BATTERY ENERGY STORAGE FIRE SAFETY | |
| Sec. 187.001. DEFINITIONS. In this chapter: | |
| (1) "Battery energy storage" means a battery energy | |
| storage facility or battery energy storage equipment considered to | |
| be a generation asset under Section 35.152(a) and operated inside | |
| or outside the ERCOT power region. | |
| (2) "Battery operator" means an electric cooperative, | |
| an electric utility, or a power generation company that owns or | |
| operates battery energy storage. | |
| (3) "Electric cooperative" and "municipally owned | |
| utility" have the meanings assigned by Section 11.003. | |
| (4) "Electric utility" and "power generation company" | |
| have the meanings assigned by Section 31.002. | |
| Sec. 187.002. FIRE SAFETY STANDARDS FOR BATTERY ENERGY | |
| STORAGE. (a) The state fire marshal shall adopt and periodically | |
| update fire safety standards and testing requirements for battery | |
| energy storage. The standards and requirements must be based on: | |
| (1) model code requirements for battery energy storage | |
| equipment or facilities; and | |
| (2) minimum standards related to the design, safety, | |
| and installation of stationary energy storage systems established | |
| by the National Fire Protection Association, such as NFPA 855. | |
| (b) Each battery operator or municipally owned utility that | |
| owns or operates battery energy storage shall ensure that the | |
| storage meets the fire safety standards and testing requirements | |
| adopted by the state fire marshal under Subsection (a) at the time | |
| of interconnection. | |
| (c) Unless expressly authorized by another statute, a | |
| municipality or county may not adopt, enforce, or maintain an | |
| ordinance, order, or rule regulating conduct in a field of | |
| regulation that is inconsistent with the fire safety standards and | |
| testing requirements adopted by the state fire marshal. An | |
| ordinance, order, or rule that violates this subsection is void and | |
| unenforceable. | |
| (d) On request by a municipality in which battery energy | |
| storage is located, or a county in which battery energy storage is | |
| located if the storage is in an unincorporated area, a battery | |
| operator that owns or operates the battery energy storage shall, at | |
| the battery operator's expense, contract with an independent, | |
| third-party engineer licensed in this state or other consultant | |
| with appropriate expertise to: | |
| (1) evaluate the design, safety, and installation of | |
| the battery energy storage before the start of commercial | |
| operations to ensure compliance with the requirements of this | |
| section; | |
| (2) produce a written report that: | |
| (A) includes the evaluation; | |
| (B) identifies any noted deficiencies in | |
| compliance with the standards adopted by the state fire marshal; | |
| and | |
| (C) recommends appropriate actions to correct | |
| deficiencies; and | |
| (3) provide the written report described by | |
| Subdivision (2) to the requesting municipality or county. | |
| (e) The battery operator must make available to the engineer | |
| or consultant and the requesting municipality or county the | |
| following documents if held or created by the battery operator: | |
| (1) documents relating to the site layout; | |
| (2) the emergency operations plan described by Section | |
| 187.003; | |
| (3) a hazard mitigation analysis for the battery | |
| energy storage; | |
| (4) any manufacturer specifications for the battery | |
| energy storage; | |
| (5) a UL 9540A report and any UL listings and | |
| associated documentation for the battery energy storage; | |
| (6) National Fire Protection Association standards, | |
| including any associated documentation, for the battery energy | |
| storage; | |
| (7) electrical drawings for the battery energy | |
| storage; | |
| (8) monitoring procedures for the battery energy | |
| storage; | |
| (9) alarm activation criteria for the battery energy | |
| storage; and | |
| (10) fire protection system documentation for the | |
| battery energy storage. | |
| (f) At least once every three years, each battery operator | |
| shall contract, at the battery operator's expense, with an | |
| independent, third-party engineer licensed in this state or other | |
| consultant with appropriate expertise to produce a fire safety | |
| inspection report for the battery operator's battery energy storage | |
| and provide the report to the municipality in which the storage is | |
| located or to the county in which the storage is located if the | |
| facility or equipment is in an unincorporated area. The report | |
| must: | |
| (1) include an evaluation of: | |
| (A) the structural integrity and weatherproofing | |
| of any enclosure at the site of the storage; | |
| (B) the maintenance schedule and any associated | |
| documentation for the storage; | |
| (C) the emergency operations plan described by | |
| Section 187.003; | |
| (D) any hazard mitigation analysis for the | |
| storage; | |
| (E) any monitoring procedures and monitoring | |
| history for the storage; | |
| (F) fire protection system inspection and | |
| testing records for the storage; and | |
| (G) the ventilation systems of the storage; and | |
| (2) identify any noted deficiencies and recommend | |
| appropriate actions to correct deficiencies. | |
| Sec. 187.003. EMERGENCY OPERATIONS PLANS FOR BATTERY ENERGY | |
| STORAGE. (a) In this section, "first responder" has the meaning | |
| assigned by Section 78B.001, Civil Practice and Remedies Code. | |
| (b) This section applies only to a battery operator or a | |
| municipally owned utility that owns or operates battery energy | |
| storage, whether standalone or colocated with another generation | |
| asset. | |
| (c) A battery operator or a municipally owned utility to | |
| which this section applies shall produce a site-specific emergency | |
| operations plan for each battery energy storage site owned or | |
| operated by the battery operator or utility. The site-specific | |
| emergency operations plan must include: | |
| (1) an identification of potential risks and hazards | |
| specific to the site; | |
| (2) a hazard mitigation analysis; | |
| (3) procedures for the safe shutdown, de-energizing, | |
| or isolation of equipment and systems under emergency conditions, | |
| including emergency procedures to be followed in case of fire; | |
| (4) procedures for handling equipment damaged in a | |
| fire or other emergency event; | |
| (5) procedures and schedules for conducting drills | |
| using the procedures listed under this subsection and documentation | |
| related to the performance of the drills; | |
| (6) procedures for communication between the operator | |
| of the storage and first responders, including procedures that | |
| facilitate communication between first responders and emergency | |
| contacts designated by the operator of the storage; and | |
| (7) emergency operations protocols to ensure safety | |
| during critical events, including protocols that provide for the | |
| safety of: | |
| (A) nearby residents; | |
| (B) neighboring properties; | |
| (C) first responders; and | |
| (D) the environment, including measures to | |
| mitigate or prevent pollution of air, soil, groundwater, or surface | |
| water. | |
| (d) The battery operator or municipally owned utility | |
| shall: | |
| (1) before starting commercial operations, provide | |
| the site-specific emergency operations plan developed under | |
| Subsection (c) to the local first responder that is responsible for | |
| providing fire protection services in the area in which the battery | |
| energy storage is located; and | |
| (2) maintain materials safety data sheets or | |
| comparable documents and the site-specific emergency operations | |
| plan developed under Subsection (c) at an on-site location | |
| accessible to personnel responsible for the operations and | |
| maintenance of the battery energy storage and first responders. | |
| (e) The battery operator or municipally owned utility shall | |
| offer to local first responders, at no cost to the responders, | |
| education and annual training regarding responding to an equipment | |
| failure incident at the battery energy storage site, including: | |
| (1) training on specific characteristics of battery | |
| energy storage technology; | |
| (2) training on protecting first responders during | |
| incident response; | |
| (3) training on hazards commonly associated with | |
| incident response; | |
| (4) training on incident response protocols, | |
| including an overview of the site-specific emergency operations | |
| plan developed under Subsection (c); and | |
| (5) an on-site review of the perimeter, major | |
| equipment, and ingress and egress to the battery energy storage | |
| site. | |
| SECTION 2. Sections 187.002 and 187.003, Utilities Code, as | |
| added by this Act, apply only to battery energy storage facilities | |
| or equipment for which interconnection is approved by the | |
| independent system operator of jurisdiction on or after January 1, | |
| 2027. | |
| SECTION 3. This Act takes effect September 1, 2025. |