SB 1323Session 2025-2026

An Act providing for the regulation of commercial data centers; imposing duties on the Pennsylvania Public Utility Commission, the Department of Human Services and the Pennsylvania Energy Development Authority; establishing the Data Center Low-Income Home Energy Assistance Program Enhancement Account and the Pennsylvania Energy Independence Account; providing for clean firm energy requirements, contract filing, commission review, disclosure requirements, backup generation standards, curtailment standards and certification and expedited interconnection for commercial data centers bringing incremental clean firm energy resources; and imposing penalties.

Printer's No. PN1717

See other bills
under the
same topic PRINTER'S NO. 1717 THE GENERAL ASSEMBLY OF PENNSYLVANIASENATE BILL No.1323 Session of 2026 INTRODUCED BY FLYNN, SAVAL, SANTARSIERO, FONTANA, BOSCOLA, MALONE, KANE AND SCHWANK, MAY 20, 2026 REFERRED TO CONSUMER PROTECTION AND PROFESSIONAL LICENSURE, MAY 20, 2026 AN ACTProviding for the regulation of commercial data centers; imposing duties on the Pennsylvania Public Utility Commission, the Department of Human Services and the Pennsylvania Energy Development Authority; establishing the Data Center Low-Income Home Energy Assistance Program Enhancement Account and the Pennsylvania Energy Independence Account; providing for clean firm energy requirements, contract filing, commission review, disclosure requirements, backup generation standards, curtailment standards and certification and expedited interconnection for commercial data centers bringing incremental clean firm energy resources; and imposing penalties.TABLE OF CONTENTSSection 1. Short title.Section 2. Definitions.Section 3. Duties of commission.Section 4. Prohibition on cost shifting and recovery of costs.Section 5. Contributions to Low-Income Home Energy Assistance Program.Section 6. Pennsylvania Energy Independence Account.Section 7. Clean firm energy requirements.Section 8. Contract filing and commission review.12345678910111213141516171819202122 Section 9. Annual report.Section 10. Disclosure requirements.Section 11. Backup generation standards.Section 12. Curtailment standards.Section 13. Certification and expedited interconnection for commercial data centers bringing incremental clean firm energy resources.Section 14. Enforcement.Section 15. Construction.Section 16. Effective date.The General Assembly of the Commonwealth of Pennsylvania hereby enacts as follows:Section 1. Short title.This act shall be known and may be cited as the Data Center Act.Section 2. Definitions.The following words and phrases when used in this act shallhave the meanings given to them in this section unless thecontext clearly indicates otherwise:"Alternative compliance payment." A per-megawatt-hour payment made by a commercial data center under section 7(e) if the commercial data center elects to satisfy its clean firm energy procurement requirement through payment in lieu of procurement."Backstop procurement of capacity." An emergency or backstop procurement of capacity by the applicable regional transmission organization or its successor organization."Clean firm energy." Energy derived from nuclear energy, hydroelectric power, including pumped storage, geothermal energy, fuel cells, solar energy, including solar energy paired 20260SB1323PN1717 - 2 - 123456789101112131415161718192021222324252627282930 with storage resources, wind energy, including wind energy paired with storage resources, clean hydrogen-fueled energy generation, battery energy storage systems and long-duration storage resources that meet all of the following:(1) The resource is dispatchable or capable of providing firm service so that the resource can deliver electricity on demand with an availability factor consistent with standards established by the commission.(2) The resource constitutes incremental capacity, including any of the following:(i) Placement in service of a new clean firm energy generation facility on or after January 1, 2025.(ii) An uprate or efficiency improvement at an existing clean firm energy generation facility completed on or after January 1, 2025, that increases accredited capacity or net output.(iii) Placement in service of a battery energy storage system on or after January 1, 2025, that provides at least two hours of continuous discharge or another duration determined by the commission to provide reliable capacity value.(iv) Placement in service of a long-duration storage resource on or after January 1, 2025, that provides not less than four hours of continuous discharge capability and firm service as determined by the commission."Clean firm energy certificate." A tradable instrument representing one megawatt-hour of eligible incremental clean firm energy, issued and retired through a registry established by the commission to demonstrate additionality and deliverability consistent with section 7 and regulations 20260SB1323PN1717 - 3 - 123456789101112131415161718192021222324252627282930 promulgated under this act."Clean firm energy generation." Electricity generated from clean firm energy. The term does not include a battery energy storage system or long-duration storage resource. The term includes solar energy paired with storage resources and wind energy paired with storage resources."Clean hydrogen." Hydrogen produced through a process that results in a lifecycle greenhouse gas emissions rate of less than four kilograms of carbon dioxide equivalent per kilogram of hydrogen."Clean oil furnace." An oil-fired furnace that meets all ofthe following:(1) Is Energy Star-certified.(2) Is designed to operate on a blended liquid fuelcontaining not less than 20% biodiesel, renewable dieselor second generation biofuel.(3) Demonstrates improved efficiency or reduced emissions relative to the system being replaced, as determined by the Department of Environmental Protection."Commercial data center." A facility, campus of facilities or array of interconnected facilities in this Commonwealth that meets all of the following:(1) Is used by a business entity or other enterprise to operate, manage or maintain a computer, group of computers or other organized assembly of hardware and software for the primary purpose of processing, storing, retrieving or transmitting data.(2) Has a peak demand of 25 megawatts or greater.(3) Is interconnected to a public utility at a single point of interconnection or multiple points of 20260SB1323PN1717 - 4 - 123456789101112131415161718192021222324252627282930 interconnection or is interconnected to multiple public utilities within this Commonwealth through multiple points of interconnection."Commission." The Pennsylvania Public Utility Commission."Community energy facility." A facility that complies with the requirements necessary to achieve designation as a community energy facility under a State law enacted on or after the effective date of this definition establishing a community energy program in this Commonwealth."Electric distribution company." As defined in 66 Pa.C.S. § 2803 (relating to definitions)."Electric generation supplier." As defined in 66 Pa.C.S. § 2803."Electric service." All interconnection services and other required elements provided by an electric distribution company for the jurisdictional transmission and distribution of electricity. The term shall be construed in a manner consistent with the meaning of service under 66 Pa.C.S. § 102 (relating to definitions) as applied to public utilities."Energy-efficient heat pump." An electric heat pump that meets or exceeds the highest efficiency tier, excluding an advanced tier, established by the Consortium for Energy Efficiency as of the effective date of this definition or a functionally equivalent program designated by the Department of Environmental Protection."Energy Star." The voluntary energy efficiencycertification program established by the United StatesEnvironmental Protection Agency and the United StatesDepartment of Energy, or any successor program, thatestablishes minimum performance and efficiency standards for20260SB1323PN1717 - 5 - 123456789101112131415161718192021222324252627282930 qualifying equipment."Fuel cell." An electrochemical device that converts chemical energy in a hydrogen-rich fuel directly into electricity, heat and water without combustion."Incremental capacity." Additional accredited capacity or additional net energy output from a clean firm energy generation resource or long-duration storage resource that meets all of the following:(1) Results from the placement in service of a new resource on or after January 1, 2025.(2) Results from an uprate or efficiency improvement completed on or after January 1, 2025, at an existing clean firm energy generation resource or long-duration storage resource, to the extent that the improvement increases accredited capacity or net output available to the grid.(3) In the case of a battery energy storage system or long-duration storage resource, results from the installation of new storage equipment or the expansion or repowering of an existing storage facility completed on or after January 1, 2025, that increases discharge duration, rated capacity or firm service capability.(4) Is verified and certified by the commission as representing additional accredited capacity or additional net energy output that would not have been available to the bulk electric system in this Commonwealth absent the investment identified under paragraph (1), (2) or (3)."Interruptible rate." A rate published in an electric distribution company's tariff and approved by the commission as just and reasonable that authorizes the electric distribution company to curtail service to customers taking service under the 20260SB1323PN1717 - 6 - 123456789101112131415161718192021222324252627282930 rate during a regional supply shortage, in response to a projected regional supply shortage, in response to actual or projected conditions on the bulk power system or under other conditions specified in the rate when, in the electric distribution company's discretion, curtailment is necessary to protect the electric distribution company's ability to provide firm electric service to customers served under other tariff rate schedules. The term includes a rate that contains provisions for coordination with a regional transmission organization voluntary or mandatory curtailment program under which load is curtailed in a preemergency condition."Lifecycle greenhouse gas emissions." The term shall have the meaning given to it under 26 U.S.C. § 45V(c)(1)(A) and (B) (relating to credit for production of clean hydrogen), as in effect on the effective date of this definition."Load-serving entity." An electric distribution company or electric generation supplier that serves retail load within the regional transmission organization in which the electric distribution company or electric generation supplier participates."Long-duration storage resource." A storage resource located within this Commonwealth that meets all of the following:(1) Is capable of delivering not less than four hours of continuous discharge at rated capacity.(2) Is dispatchable or capable of providing firm service consistent with standards established by the commission.(3) Qualifies as incremental capacity placed in service on or after January 1, 2025."Low-Income Home Energy Assistance Program." A federally funded program that provides financial assistance in the form of 20260SB1323PN1717 - 7 - 123456789101112131415161718192021222324252627282930 cash and crisis grants to low-income households for home energy bills and is administered by the Department of Human Services."Material adverse impact." A demonstrable and significant effect on electric bill affordability for residential customers, as determined by the commission by regulation or order, considering rate levels, cumulative riders and surcharges and income-based affordability metrics."Pennsylvania Energy Development Authority." The authority established under section 2803-C of the act of April 9, 1929 (P.L.177, No.175), known as The Administrative Code of 1929."Pennsylvania Energy Independence Account." The restricted account established under section 6(a)."Public utility." As defined in 66 Pa.C.S. § 102."Ratepayer." A retail customer of an electric distribution company that purchases electric delivery service."Regional supply shortage." A condition in which supply reserves are less than target supply reserves as determined by the regional transmission organization."Regional transmission organization." An entity approved by the Federal Energy Regulatory Commission to control and operate electric transmission facilities in interstate commerce and ensure nondiscriminatory access to those facilities."Renewable natural gas device." A device that generates electricity using a fuel source consisting of at least 75% biodiesel or biogas, including biogas derived from municipal solid waste, industrial waste, food waste, wastewater treatment material and animal manure resulting from the decomposition of organic matter under anaerobic conditions, or any methane resource classified as a Tier I alternative energy source as defined in section 2 of the act of November 30, 2004 (P.L.1672, 20260SB1323PN1717 - 8 - 123456789101112131415161718192021222324252627282930 No.213), known as the Alternative Energy Portfolio Standards Act, the principal constituents of which are methane and carbon dioxide, that has been upgraded for use in place of fossil natural gas, gasoline or diesel fuel."Small-scale energy system." A system with a nameplate capacity rating that does not exceed two megawatts and that generates or stores electricity by means of solar panels, batteries or renewable natural gas devices, or a combination of those resources. The term includes an energy-efficient heat pump or clean oil furnace installed at a home or residential building, a small business as defined in 62 Pa.C.S. § 2102 (relating to definitions), a charitable organization as defined in section 3 of the act of December 19, 1990 (P.L.1200, No.202), known as the Solicitation of Funds for Charitable Purposes Act, an educational institution, a religious institution, a municipal building or a State government building."Universal service and energy conservation." As defined in 66 Pa.C.S. § 2803 for electric service and 66 Pa.C.S. § 2202 (relating to definitions) for natural gas service."Useful life." For purposes of cost allocation and recovery under this act, the depreciable life used in commission-approved cost recovery or a period determined by the commission.Section 3. Duties of commission.(a) Temporary regulations.--(1) To facilitate the prompt implementation of this act, the commission shall promulgate temporary regulations no later than 90 days after the effective date of this subsection. The commission shall transmit notice of the promulgation of the temporary regulations to the Legislative Reference Bureau for publication in the next available issue 20260SB1323PN1717 - 9 - 123456789101112131415161718192021222324252627282930 of the Pennsylvania Bulletin.(2) Temporary regulations promulgated under this subsection shall expire no later than two years after publication in the Pennsylvania Bulletin.(3) The commission may promulgate temporary regulations under this subsection that are not subject to any of the following:(i) Section 612 of the act of April 9, 1929 (P.L.177, No.175), known as The Administrative Code of 1929.(ii) Sections 201, 202, 203, 204 and 205 of the act of July 31, 1968 (P.L.769, No.240), referred to as the Commonwealth Documents Law.(iii) Sections 204(b) and 301(10) of the act of October 15, 1980 (P.L.950, No.164), known as the Commonwealth Attorneys Act.(iv) The act of June 25, 1982 (P.L.633, No.181), known as the Regulatory Review Act.(4) The commission's authority to promulgate temporary regulations under this subsection shall expire two years after the effective date of this subsection. Before the expiration of this authority, the commission shall promulgate final regulations in accordance with State law and subsection (b).(b) Required regulatory topics.--Regulations promulgated under subsection (a) shall include provisions governing all of the following:(1) Retail tariff terms and conditions between a commercial data center and an electric distribution company for electric service to safeguard existing customers from 20260SB1323PN1717 - 10 - 123456789101112131415161718192021222324252627282930 stranded investment and cost shifting, including all of the following:(i) Deposits or other financial security required from a commercial data center.(ii) Contributions in aid of construction for network upgrades or distribution infrastructure and direct assignment through rates of costs for transmission service, to the extent permitted by law.(iii) Minimum contract terms and minimum load obligations that require a commercial data center, if the commercial data center ceases operations before satisfying the minimum contract term or engages in economic peak-shaving behavior, to take a minimum level of service for a minimum number of years sufficient to generate expected revenues that protect other customers. An electric distribution company shall require the commercial data center to secure the obligation under this subparagraph by a letter of credit or other comparable financial instrument that ensures payment if the commercial data center ceases operations or otherwise fails to satisfy the obligation.(iv) Load-ramping schedules to ensure infrastructure adequacy.(v) Exit fees or early termination fees.(vi) Measures to prevent circumvention of the commercial data center threshold through multiple facilities, interconnection points or metering points.(vii) Tracking of all costs, including transmission and distribution costs, incurred to serve a commercial data center and verification that the revenues collected 20260SB1323PN1717 - 11 - 123456789101112131415161718192021222324252627282930 exceed the costs incurred.(viii) An end-of-contract process that provides sufficient notice of a commercial data center's renewal or closure.(ix) To the extent permitted by Federal and State law, a process for the direct assignment to a commercial data center of costs assigned by a regional transmission organization, as determined by the commission.(2) Curtailment of a commercial data center's load under an interruptible rate.(3) Standards governing coordination of an electric distribution company's interruptible rate with a regional transmission organization voluntary or mandatory curtailment program to ensure statewide consistency.(4) Conditions for interconnection of new commercial data center load while ensuring the continued provision of electric service to existing customers that is adequate, reasonable, reasonably continuous and without unreasonable interruption or delay. If a regional supply shortage exists or is likely to exist, as forecasted or determined by the regional transmission organization in which the electric distribution system participates, the commission shall impose any of the following conditions on a new interconnection or an incremental addition of load associated with an interconnected commercial data center:(i) Requiring the commercial data center to take electric distribution service under the electric distribution company's interruptible rate.(ii) Permitting firm electric distribution service on the condition that the commercial data center has been 20260SB1323PN1717 - 12 - 123456789101112131415161718192021222324252627282930 certified to have brought its own incremental clean firm energy resources into service under a certification program established by the commission, the Federal Energy Regulatory Commission or the regional transmission organization or independent system operator in which the applicable public utility participates.(iii) Imposing a combination of the requirements under subparagraphs (i) and (ii).(5) Cost responsibility standards under section 4.(6) Establishment of the alternative compliance payment rate and calculation methods under section 7(e).(7) Disclosure requirements under section 10.(8) Backup generation standards under section 11.(9) Curtailment standards under section 12.(10) Certification and expedited interconnection standards under section 13.Section 4. Prohibition on cost shifting and recovery of costs.(a) Prohibition on cross-subsidization.--An electric distribution company may not recover from ratepayers other than commercial data centers, whether through base rates, riders, surcharges or another ratemaking mechanism, a cost caused in whole or in part by the interconnection, service or load of a commercial data center, including a cost associated with capacity, energy, ancillary services, transmission, distribution, network upgrades or dedicated facilities, if either of the following applies:(1) The cost is directly attributable to the provision of electric service to a commercial data center.(2) The cost would not have been incurred but for the electricity demand of a commercial data center.20260SB1323PN1717 - 13 - 123456789101112131415161718192021222324252627282930 (b) Rate review and allocation.--The commission shall review rates to ensure that the cost of providing service to a commercial data center is not subsidized by another customer class. For purposes of a rate determination, each electric distribution company serving a commercial data center shall have the following duties:(1) To allocate or assign costs in one of the following ways:(i) Allocate the cost of serving commercial data centers to a customer class consisting solely of commercial data centers in an amount equal to the cost of serving commercial data centers, including direct and indirect costs associated with providing service to commercial data centers through new or existing facilities.(ii) Directly assign the cost of serving a commercial data center to the commercial data center.(2) To mitigate the risk of any of the following:(i) Another electric service customer paying a cost associated with providing service to a commercial data center if the cost does not benefit another customer class.(ii) Shifting to another electric service customer the cost of serving a commercial data center, including a cost incurred by an electric distribution company to meet load requirements resulting from the provision of electric service to a commercial data center.(c) Cost-of-service study.--A public utility that serves or is reasonably expected to serve commercial data center load shall submit a full cost-of-service study when seeking a rate 20260SB1323PN1717 - 14 - 123456789101112131415161718192021222324252627282930 increase under 66 Pa.C.S. § 1308 (relating to voluntary changes in rates) to support the public utility's proposed allocation of shared or indirect costs that benefit multiple customer classes, including commercial data centers.(d) Universal service and energy conservation programs.--A public utility shall recover from commercial data centers the costs incurred by the public utility in connection with the development, implementation and support of universal service and energy conservation programs, consistent with 66 Pa.C.S. §§ 2203(6), (7), (8), (9) and (10) (relating to standards for restructuring of natural gas utility industry) and 2804(8) and (9) (relating to standards for restructuring of electric industry), through a tariff rate approved by the commission.(e) Duration of allocation and recovery standards.--The commission shall establish standards to ensure that a commercial data center responsible for costs specified under subsection (a), including construction, transmission and distribution costs, remains responsible for those costs for the useful life of the associated infrastructure or for the duration of the service obligation, whichever is longer, in a manner that supports business development in this Commonwealth while minimizing the risk of stranded infrastructure costs, maintaining customer affordability and maintaining overall system reliability.(f) Transmission and regional cost impacts.--To the maximum extent permitted under Federal law, the commission shall ensure that a cost allocated to an electric distribution company or electric generation supplier under a tariff approved by the Federal Energy Regulatory Commission and associated with transmission facilities, network upgrades, capacity obligations 20260SB1323PN1717 - 15 - 123456789101112131415161718192021222324252627282930 or another regional system cost, if caused in whole or in part by a commercial data center, is appropriately allocated at retail and recovered from the commercial data center and does not result in unreasonable cost impacts to residential customers or small commercial customers.(g) Curtailment obligations.--(1) If a regional transmission organization issues a curtailment obligation or directive and assigns the obligation or directive to an electric distribution company or electric generation supplier in its capacity as a load-serving entity, in whole or in part due to the provision of electric service to a commercial data center, the electric distribution company or electric generation supplier shall require the commercial data center to satisfy the curtailment obligation or directive under contractual terms or tariff provisions approved by the commission.(2) Another customer of the electric distribution company or electric generation supplier may not be assigned responsibility for a curtailment obligation resulting from the commercial data center's service.(3) Nothing in this subsection shall be construed to:(i) prevent or hinder an electric distribution company or electric generation supplier from taking action necessary to maintain system reliability; or(ii) prohibit an electric distribution company or electric generation supplier from implementing a voluntary load curtailment program approved by the commission.(h) Backstop procurement obligations.--(1) If a regional transmission organization undertakes 20260SB1323PN1717 - 16 - 123456789101112131415161718192021222324252627282930 backstop procurement of capacity or a comparable reliability service and assigns a financial or other obligation to an electric distribution company or electric generation supplier in its capacity as a load-serving entity, in whole or in part due to a commercial data center's service, the electric distribution company or electric generation supplier shall allocate the obligation at retail to and recover the obligation from the commercial data center or commercial data centers that gave rise to the obligation under terms comparable to those under which the obligation is assigned to the electric distribution company or electric generation supplier.(2) If an electric distribution company does not provide retail default service to a commercial data center and, in its capacity as a load-serving entity, receives an assignment of cost obligations related to backstop procurement from a regional transmission organization, the electric distribution company may establish a nonbypassable surcharge to pass through the obligation on a pro rata basis to each commercial data center taking electric service under the electric distribution company's tariff if the rebuttable presumption under subsection (i)(2) applies.(i) Regional generation, capacity and reliability costs.--(1) To the maximum extent permitted under Federal law, if a regional transmission organization assigns, under a tariff approved by the Federal Energy Regulatory Commission, to an electric distribution company or electric generation supplier in its capacity as a load-serving entity a cost associated in whole or in part with the procurement of new generation supply, capacity or a comparable reliability 20260SB1323PN1717 - 17 - 123456789101112131415161718192021222324252627282930 service undertaken to meet the electricity demand of one or more commercial data centers, the electric distribution company or electric generation supplier shall directly assign, allocate and recover the cost from the applicable commercial data center or commercial data centers.(2) There shall be a rebuttable presumption that a cost described under paragraph (1) is attributable to a commercial data center if any of the following apply:(i) The regional transmission organization or its independent market monitor identifies the load addition as a material driver of the procurement.(ii) The timing of the procurement is reasonably correlated with the commercial data center's load addition.(iii) The procurement would not have occurred in substantially the same form or time frame absent the commercial data center's load addition.(3) The presumption under paragraph (2) shall apply solely to retail allocation and recovery by the commission and may not be construed to alter an assignment or determination made under a tariff approved by the Federal Energy Regulatory Commission.(4) If a regional transmission organization does not directly allocate the costs described under paragraph (1) to the commercial data center or commercial data centers that gave rise to the costs, the commission shall establish and implement, consistent with Federal law, a just and reasonable mechanism to allocate and recover the costs from the applicable commercial data center or commercial data centers without altering the wholesale assignment established under a 20260SB1323PN1717 - 18 - 123456789101112131415161718192021222324252627282930 tariff approved by the Federal Energy Regulatory Commission.(5) If an electric distribution company does not provide retail default service to a commercial data center and, in its capacity as a load-serving entity, receives an assignment of generation supply, capacity or comparable reliability service cost obligations from a regional transmission organization, the electric distribution company may establish a nonbypassable surcharge to pass through the obligation on a pro rata basis to each commercial data center taking service under the electric distribution company's tariff if the rebuttable presumption under paragraph (2) applies.(j) Financial security.--(1) As a condition of taking electric service, a commercial data center whose load is reasonably likely to trigger or contribute to an obligation under subsection (h) shall provide financial security, in a form and amount approved by the commission, sufficient to ensure that existing and future customers of the public utility are held harmless for the full term and value of the obligation.(2) The financial security required under paragraph (1) shall remain in effect for the duration of the applicable capacity obligation and any associated cost recovery period.(3) As a condition of taking electric service, a commercial data center reasonably expected to trigger or contribute to a cost described under subsection (i) shall provide and maintain financial security, in a form and amount approved by the commission, sufficient to ensure full recovery of the cost for the duration of the obligation and to hold harmless existing and future customers of the electric distribution company.20260SB1323PN1717 - 19 - 123456789101112131415161718192021222324252627282930 (k) Duration of responsibility.--Cost responsibility under subsections (h) and (i) shall apply for the useful life of the associated facilities or the duration of the regional obligation, whichever is longer.(l) Federal law.--Nothing in subsections (g), (h), (i), (j) and (k) shall be construed to conflict with or preempt the jurisdiction of the Federal Energy Regulatory Commission or to require an electric distribution company or electric generation supplier to take action inconsistent with a tariff approved by the Federal Energy Regulatory Commission.(m) Implementation.--The commission shall promulgate regulations or issue orders necessary to implement subsections (g), (h), (i), (j), (k) and (l) in a manner consistent with Federal law governing regional transmission organizations and applicable tariffs and agreements.(n) Alternative compliance payments not recoverable.--An electric distribution company may not recover, through base rates, riders, surcharges or another ratemaking mechanism, an alternative compliance payment under section 7(e) from a ratepayer other than the commercial data center responsible for the payment.Section 5. Contributions to Low-Income Home Energy Assistance Program.(a) Establishment of account.--The Data Center Low-Income Home Energy Assistance Program Enhancement Account is established as a restricted account in the General Fund. The Department of Human Services shall use money appropriated from the Data Center Low-Income Home Energy Assistance Program Enhancement Account under subsection (d) for a supplemental program to enhance the Low-Income Home Energy Assistance 20260SB1323PN1717 - 20 - 123456789101112131415161718192021222324252627282930 Program. The supplemental program shall include a summer cooling component.(b) Sources of money.--The following shall be deposited into the Data Center Low-Income Home Energy Assistance Program Enhancement Account:(1) Payments made under subsection (c).(2) Interest accrued on money in the Data Center Low-Income Home Energy Assistance Program Enhancement Account.(3) Money from another source authorized by Federal or State law.(c) Annual payments.--(1) No later than June 1 of each year, each commercial data center with an annual peak load of at least 25 megawatts shall pay into the Data Center Low-Income Home Energy Assistance Program Enhancement Account as follows:(i) $40,000 per megawatt of annual peak load up to and including 25 megawatts.(ii) For each additional megawatt of annual peak load above 25 megawatts, an additional $40,000 per megawatt.(2) A payment under this subsection shall be required for the duration of the load.(3) The commission may adjust the payment amounts under this subsection periodically to account for inflation. The commission shall make an adjustment under this paragraph by promulgating regulations.(d) Appropriation.--Money in the Data Center Low-Income Home Energy Assistance Program Enhancement Account is appropriated to the Department of Human Services on a continuing basis for the purposes of this section.20260SB1323PN1717 - 21 - 123456789101112131415161718192021222324252627282930 (e) Regulations and guidelines.--The Department of Human Services may promulgate regulations or issue guidelines necessary to implement this section.Section 6. Pennsylvania Energy Independence Account.(a) Establishment of account.--The Pennsylvania Energy Independence Account is established as a restricted account in the General Fund. The Pennsylvania Energy Development Authority shall expend money from the Pennsylvania Energy Independence Account for the purposes of this act and may establish subaccounts within the Pennsylvania Energy Independence Account.(b) Sources of money.--The following shall be deposited into the Pennsylvania Energy Independence Account:(1) Money appropriated or transferred by the General Assembly for deposit into the Pennsylvania Energy Independence Account.(2) Supplemental Federal funding available for the purposes of this act and appropriated by the General Assembly for deposit into the Pennsylvania Energy Independence Account.(3) Interest and other amounts resulting from the investment of money in the Pennsylvania Energy Independence Account.(4) Gifts, grants and donations made to the Pennsylvania Energy Independence Account.(c) Use of money.--Money in the Pennsylvania Energy Independence Account is appropriated to the Pennsylvania Energy Development Authority on a continuing basis to provide grants, loans and loan guarantees to finance new clean firm energy systems, small-scale energy systems, energy efficiency projects and community energy facilities.20260SB1323PN1717 - 22 - 123456789101112131415161718192021222324252627282930 (d) Construction loans.--The Pennsylvania Energy Development Authority may provide a construction loan under this section only if the loan constitutes the senior debt secured by the facility and does not exceed 60% of the facility's estimated construction cost.(e) Administrative costs.--The Pennsylvania Energy Development Authority may use not more than 5% annually of the money in the Pennsylvania Energy Independence Account for administrative costs relating to the authority's responsibilities under this act.(f) Application criteria.--In evaluating an application for a loan under this section, the Pennsylvania Energy Development Authority shall consider all of the following:(1) The applicant's:(i) quality of services and management;(ii) efficiency of operations;(iii) history of operations in this Commonwealth and the United States;(iv) resource operation attributes;(v) ability to address regional, local and reliability needs;(vi) access to resources essential for operating the project for which the loan is requested, including land, water and reliable infrastructure, as applicable; and(vii) evidence of creditworthiness and ability to repay the loan on the terms established in the loan agreement, including total assets, total liabilities, net worth and credit ratings issued by major credit rating agencies.(2) The generation capacity and estimated cost of the 20260SB1323PN1717 - 23 - 123456789101112131415161718192021222324252627282930 project for which a grant, loan or loan guarantee is requested.(3) Any other factor the Pennsylvania Energy Development Authority considers appropriate.(g) Annual payments.--(1) No later than June 1 of each year, each commercial data center with an annual peak load of at least 25 megawatts shall pay into the Pennsylvania Energy Independence Account as follows:(i) $2,000 per megawatt of annual peak load up to and including 25 megawatts.(ii) For each additional megawatt of annual peak load above 25 megawatts, an additional $2,000 per megawatt.(2) A payment under this subsection shall be required for the duration of the load.(3) The commission may adjust the payment amounts under this subsection periodically to account for inflation. The commission shall make an adjustment under this paragraph by promulgating regulations.(h) Exemption.--A commercial data center certified by the commission under section 13 to have brought its own incremental clean firm energy resources shall be exempt from subsection (g).Section 7. Clean firm energy requirements.(a) Procurement requirement.--Energy supplied to a commercial data center shall include electricity procured from incremental clean firm energy resources located within this Commonwealth in an amount not less than the following percentages of the commercial data center's annual electricity consumption:20260SB1323PN1717 - 24 - 123456789101112131415161718192021222324252627282930 (1) Beginning January 1, 2027, 10%.(2) Beginning January 1, 2030, 14.5%.(3) Beginning January 1, 2035, 32%.(b) Incremental requirement.--As certified by the commission, only incremental capacity or incremental net additional megawatt-hours delivered to the grid relative to a baseline year may qualify to satisfy subsection (a).(c) Compliance methods.--A commercial data center may demonstrate compliance with this section through any of the following:(1) A power purchase agreement or other bilateral contract for clean firm energy.(2) Retirement of a clean firm energy certificate issued through a registry established by the commission.(3) Another method or instrument approved by the commission.(d) Cost containment and flexibility.--To protect system reliability and ratepayer affordability, the commission shall have the following duties:(1) Establish an alternative compliance payment available to a commercial data center.(2) Permit the banking of clean firm energy certificates for up to three compliance years.(3) Authorize limited borrowing of future-year certificates under conditions determined by the commission.(4) Temporarily adjust the percentages under subsection (a) if the commission determines that insufficient eligible in-State supply of clean firm energy exists for a compliance year, if the commission issues written findings and a schedule for restoring full compliance with this section.20260SB1323PN1717 - 25 - 123456789101112131415161718192021222324252627282930 (e) Alternative compliance payment.--(1) A commercial data center that does not procure or demonstrate retirement of sufficient clean firm energy certificates to satisfy subsection (a) for a compliance year shall make an alternative compliance payment to the Pennsylvania Energy Independence Account established under section 6.(2) The commission shall establish the rate of the alternative compliance payment by regulation. The rate shall be expressed in dollars per megawatt-hour and shall be calculated in a manner that does all of the following:(i) Ensures that the alternative compliance payment is a viable cost containment mechanism for commercial data centers.(ii) Reflects the commission's assessment of the market cost of incremental clean firm energy resources.(iii) Supports the Commonwealth's interest in facilitating timely investment in clean firm energy and long-duration storage resources located within this Commonwealth.(3) An alternative compliance payment under this subsection shall be deposited into the Pennsylvania Energy Independence Account and used for the purposes specified in section 6(c), including grants, loans and loan guarantees to finance new clean firm energy systems, energy efficiency projects, small-scale energy systems, community energy facilities and other projects that support energy reliability and independence in this Commonwealth.(4) Payment of an alternative compliance payment under this subsection shall constitute full compliance with 20260SB1323PN1717 - 26 - 123456789101112131415161718192021222324252627282930 subsection (a) for the corresponding megawatt-hours.Section 8. Contract filing and commission review.(a) Filing requirement.--An electric distribution company shall file with the commission a copy of each contract executed with a commercial data center on or after the effective date of this subsection, including any of the following:(1) A contract for electric service between a public utility and a commercial data center entered into under a commission-approved rate schedule for distribution service.(2) A construction services agreement, engineering services agreement or similar agreement between a public utility and a commercial data center relating to the public utility's high-voltage transmission infrastructure or distribution infrastructure.(3) A construction services agreement, engineering services agreement or similar agreement between a public utility and a commercial data center relating to transmission infrastructure that is the subject of the public utility's application for commission approval and authorization to locate and construct a transmission line or a portion of a transmission line with a design voltage greater than 100,000 volts.(b) Distribution of filed contracts.--A public utility shall provide a copy of a contract filed under subsection (a) to the Office of Consumer Advocate, the Office of Small Business Advocate and the Bureau of Investigation and Enforcement within the commission, subject to an appropriate confidentiality agreement, protective agreement or protective order.(c) Supporting documentation.--An electric distribution company shall include with a filing under subsection (a) 20260SB1323PN1717 - 27 - 123456789101112131415161718192021222324252627282930 sufficient documentation to permit the commission to conduct the review required under subsection (d).(d) Commission review.--The commission shall review each contract filed under this section to determine all of the following:(1) The impact of the contract on the continued provision of electric service that is adequate, safe and reliable to residents and businesses of this Commonwealth.(2) The impact of the contract on ratepayers and electric bill affordability for residential customers and commercial customers. The impact on low-income customers shall be determined as a subset of residential customers.(3) Whether the contract is reasonably likely to result in a material adverse impact on electric bill affordability or reliability for residential customers.(4) Whether the contract complies with sections 3, 4 and 7.(e) Approval standard.--The commission may not approve a contract under this act if the commission finds that the contract is reasonably likely to result in a material adverse impact on electric bill affordability or reliability for residential customers. As a condition of approval, the commission may require the imposition of any reasonable mitigation measure necessary to ensure that the contract will not result in a material adverse impact on electric bill affordability or reliability for residential customers.Section 9. Annual report.(a) Report.--For at least 10 years, the commission shall submit a written report to the General Assembly each year and shall make a public version of the report available on the 20260SB1323PN1717 - 28 - 123456789101112131415161718192021222324252627282930 commission's publicly accessible Internet website.(b) Contents.--The report shall include all of the following:(1) The commission's efforts during the prior year to implement this act.(2) The commission's determinations under section 8(d) regarding the impact of commercial data centers on the continued provision of electric service that is adequate, safe and reliable to residents and businesses of this Commonwealth, the impact on ratepayers and electric bill affordability and compliance with sections 3, 4 and 7.(3) Recommendations for legislative or regulatory changes to improve the commission's oversight responsibilities under this act.Section 10. Disclosure requirements.(a) Interconnection requests.--The commission shall require each planned commercial data center to disclose to the commission, the applicable electric distribution company and the applicable regional transmission organization or independent system operator whether the planned commercial data center is pursuing a substantially similar request for electric service within this Commonwealth or within the applicable regional transmission organization or independent system operator if approval of the substantially similar request would result in a change, delay or withdrawal of the interconnection request. The disclosure may withhold or anonymize competitively sensitive details. The commission shall prohibit or impose reasonable restrictions on the sale or disclosure of information provided to an electric distribution company under this subsection.(b) Backup generation.--The commission shall require each 20260SB1323PN1717 - 29 - 123456789101112131415161718192021222324252627282930 planned commercial data center to disclose to the commission, the applicable electric distribution company and the applicable regional transmission organization or independent system operator information regarding the planned commercial data center's backup generation resources and storage resources and the planned commercial data center's capability to rely on backup generation resources or storage resources during a period of required load shedding or curtailment, including the amount of notice required to deploy backup generation resources or storage resources.Section 11. Backup generation standards.A commercial data center's onsite fossil-fueled backup generation shall comply with all of the following:(1) Meet or exceed the Tier 4 emissions standards of the United States Environmental Protection Agency or both meet the Tier 2 emissions standards and be equipped with a selective catalytic reduction system or another emissions control system that more stringently reduces nitrogen oxides, where applicable.(2) Be limited to emergency use and limited testing and maintenance consistent with Federal and State air quality laws and regulations.(3) Be permitted, monitored and reported in the aggregate as a single emissions source or as part of a single emissions source, where practicable, in coordination with the Department of Environmental Protection.Section 12. Curtailment standards.(a) Direction to commercial data centers.--During a period of emergency curtailment or manual load dump, the commission shall require an electric distribution company to direct a 20260SB1323PN1717 - 30 - 123456789101112131415161718192021222324252627282930 commercial data center to deploy backup generation resources or storage resources or curtail load before the electric distribution company curtails service to a residential customer or small commercial customer.(b) Priority.--The commission may require an electric distribution company to give priority under subsection (a) to a commercial data center that has not been certified to have brought its own incremental clean firm energy resources into service under a program established by the commission, the Federal Energy Regulatory Commission or the regional transmission organization or independent system operator in which the applicable public utility participates.(c) Environmental compliance.--Nothing in this section shall be construed to authorize or require a violation of a Federal or State emissions limitation or another Federal or State environmental law or regulation.Section 13. Certification and expedited interconnection for commercial data centers bringing incremental clean firm energy resources.(a) Certification program.--The commission shall establish a program to certify a commercial data center that has brought or plans to bring incremental clean firm energy resources. Certification shall be based on a binding financial commitment by the commercial data center, including a power purchase agreement, to enable incremental clean firm energy resources on a one-for-one accredited unforced capacity basis, including a reasonable reserve margin, tied to the commercial data center's ramp-up and utilization schedule, through any combination of the following:(1) Placement in service by the commercial data center 20260SB1323PN1717 - 31 - 123456789101112131415161718192021222324252627282930 or a third party of an incremental clean firm energy resource or combined generation and storage resource within the regional transmission organization that serves the commercial data center.(2) An uprate or expansion of an existing clean firm energy resource or combined generation and storage resource within the regional transmission organization that serves the commercial data center, to the extent of the additional accredited unforced capacity.(3) Participation in a demand response product, if the participation continues for the duration of the certification period or until the commercial data center has brought additional accredited unforced capacity equivalent to the capacity value of the demand response product.(4) Another incremental addition of accredited unforced capacity from incremental clean firm energy resources, as measured by the applicable regional transmission organization or independent system operator.(b) Interconnection priority.--The commission shall require an electric distribution company to give priority to the interconnection of a commercial data center certified under subsection (a). For an interconnection subject to State jurisdiction, the commission shall also require an electric distribution company to give priority to the interconnection of an incremental clean firm energy resource or combined generation and storage resource associated with a certified commercial data center.Section 14. Enforcement.A violation of this act shall be subject to enforcement by the commission under 66 Pa.C.S. Ch. 33 (relating to violations 20260SB1323PN1717 - 32 - 123456789101112131415161718192021222324252627282930 and penalties).Section 15. Construction.Nothing in this act shall be construed to authorize an electric distribution company to own electric generation supply in this Commonwealth.Section 16. Effective date.This act shall take effect in 60 days.20260SB1323PN1717 - 33 - 1234567

Official text from the Pennsylvania Legislature. Formatting has been adapted for reading on Ratifi.