PRINTER'S NO. 3926 THE GENERAL ASSEMBLY OF PENNSYLVANIAHOUSE BILL No.2828 Session of 2026 INTRODUCED BY FIEDLER, PIELLI, GIRAL, PROBST, HANBIDGE, DONAHUE, WAXMAN, RIVERA, HILL-EVANS, CEPEDA-FREYTIZ, PASHINSKI, MADDEN, BOYD, INGLIS AND MULLINS, SEPTEMBER 24, 2026 REFERRED TO COMMITTEE ON ENERGY, SEPTEMBER 25, 2026 AN ACTProviding for tariffs for large computational load customers and for emergency load control procedures during regional resource adequacy shortfalls; and imposing duties on the Pennsylvania Public Utility Commission.The General Assembly of the Commonwealth of Pennsylvania hereby enacts as follows:Section 1. Short title.This act shall be known and may be cited as the Large Computational Load Customer and Consumer Protection Act.Section 2. Definitions.The following words and phrases when used in this act shall have the meanings given to them in this section unless the context clearly indicates otherwise:"Bring your own new capacity." The standard for a large computational load customer to secure new capacity resources to meet its electric demand. The term shall have the same meaning as defined in PJM's Interim Resource Adequacy Service tariff filing with the Federal Energy Regulatory Commission at Docket 123456789101112131415161718

No. ER26-3515, including modifications to the definition upon Federal Energy Regulatory Commission approval of the filing or any successor filings that are substantially consistent with the purpose of PJM's Interim Resource Adequacy tariff filing."Commission." The Pennsylvania Public Utility Commission."Contract capacity." The mutually agreed peak demand of a large computational load customer for which an electric distribution company provides service, as specified in a service agreement."Delivery year." The 12-month period beginning on June 1 of one calendar year and ending on May 31 of the next calendar year, as used by PJM."Electric distribution company." As defined in 66 Pa.C.S. § 2803 (relating to definitions)."Exit fee." A dollar amount equal to the minimum monthly bill due from a large computational load customer to an electric distribution company under a service agreement multiplied by the number of months remaining in the service agreement term at the time of termination or reduction in contract capacity."Incremental cost." The total costs caused in whole or in part by a large computational load customer that would not have been incurred but for the electricity demand of the large computational load customer and that are directly attributable to the provision of electric service to the large computational load customer. The term includes the cost of infrastructure upgrades or improvements and service associated with capacity, energy, ancillary services, transmission, distribution and dedicated facilities."Interim Resource Adequacy Service" or "IRAS." A load reduction program implemented jointly between PJM and electric 20260HB2828PN3926 - 2 - 123456789101112131415161718192021222324252627282930

distribution companies prior to an energy emergency level 1 action designated by the North American Electric Reliability Corporation, through which eligible new large computational load customers that have not made arrangements to secure bring your own new capacity resources shall provide load reductions to avoid escalation of emergency procedures, as described in PJM's Interim Resource Adequacy Service tariff filing with the Federal Energy Regulatory Commission under Docket No. ER26-3515, including modifications as may be made to the program upon Federal Energy Regulatory Commission approval or any successor programs that are substantially consistent with the purpose of PJM's Interim Resource Adequacy Service tariff filing."Large computational load customer." A customer with electric demand greater than 25 megawatts at a single location or demanding greater than 100 megawatts in the aggregate within a limited geographic region no larger than 0.5 square miles, where in either case the electric demand is primarily to support information technology equipment, including data storage and network hardware or by successor tariff definitions as established by the commission."PJM." PJM Interconnection, L.L.C., regional transmission organization or its successor."Planning horizon." A future period when, for system planning purposes, power demand and supply are forecasted based on reasonable assumptions about future conditions."Reliability backstop auction." The central procurement administered by PJM to procure capacity resources to address a forecasted resource adequacy shortfall, as described in the PJM tariff filing with the Federal Energy Regulatory Commission at Docket No. ER26-3380, including modifications as may be made to 20260HB2828PN3926 - 3 - 123456789101112131415161718192021222324252627282930

the program upon Federal Energy Regulatory Commission approval or any successor capacity procurements to address a forecasted resource adequacy shortfall attributed primarily to load growth from large computational load customers."Resource adequacy shortfall." A circumstance, as determined by PJM in the planning horizon, in which there is insufficient electric capacity to meet the reliability needs of the PJM region for a delivery year."Service agreement." Any form of contractual agreement under which an electric distribution company provides electric service to a large computational load customer.Section 3. Tariff for large computational load customers.(a) Prohibition of cost-shifting.--The incremental cost attributable to a large computational load customer may not be recovered, in whole or in part, from other customer classes.(b) Tariff filing and approval.--Within 90 days of the effective date of this subsection, each electric distribution company operating in this Commonwealth shall file a tariff with the commission addressing rates and terms for large computational load customers. The commission shall approve or modify the electric distribution company's large computational load customer tariff submission within 120 days after the public process as determined by the commission.(c) Tariff requirements.--An electric distribution company's large computational load customer tariff approved by the commission shall comply with subsection (a) and, at a minimum, with the following:(1) Require a service agreement to have a term of at least 15 years, inclusive of a load ramp period.(2) Enable a large computational load customer to 20260HB2828PN3926 - 4 - 123456789101112131415161718192021222324252627282930

designate a load ramp schedule over a period of up to five years.(3) Establish a minimum monthly billing demand, in megawatts, of at least 80% of a large computational load customer's contract capacity.(4) Establish a demand charge, in dollars per megawatt-month, which, when multiplied by the minimum monthly billing demand, is sufficient to recover the component of the incremental cost of serving a large computational load customer that does not vary based on its energy consumption and is not recovered through other methods.(5) Establish a minimum monthly bill, in dollars per month, which, when applied over the duration of the service agreement term, is estimated to be sufficient to recover the incremental cost incurred to serve the customer that is not otherwise recovered through direct payments. The minimum monthly bill shall include, at a minimum, the customer charge, the product of the minimum monthly billing demand and the demand charge and a charge based on the customer's volumetric energy consumption.(6) Assign the full costs of all distribution and transmission upgrades or improvements to a large computational load customer of which the customer primarily receives the benefits and would not have been required but for the interconnection of the customer, regardless of whether other customers will benefit from the upgrades or improvements. A large computational load customer shall pay for the full costs through a contribution in aid of construction provided prior to the start of construction of the infrastructure improvements or upgrades. A contribution 20260HB2828PN3926 - 5 - 123456789101112131415161718192021222324252627282930

in aid of construction may not be included in the electric distribution company's rate base.(7) Prior to entering into a service agreement with an electric distribution company, require a large computational load customer to demonstrate site control and any additional project development milestones necessary to demonstrate a reasonable degree of project readiness, as determined by the commission.(8) Allow a large computational load customer, without the payment of a fee or penalty, to reduce its contract capacity beginning five years after the service agreement commencement date, with at least 48 months written notice, by the following amounts:(i) No more than 10% if the reduced capacity is not reassigned to another customer.(ii) No more than 25% if the full amount of contract capacity being reduced is reassigned to another customer.(9) Require a large computational load customer that terminates its service agreement or reduces its contract capacity beyond the amounts specified in subsection (c)(8) to pay at least the amount of the exit fee if the customer provides at least 48 months written notice, or to pay at least two times the exit fee if the customer fails to provide at least 48 months written notice.(10) Require a large computational load customer to provide collateral in an amount equal to 50% of the minimum monthly bill multiplied by the number of months remaining in the service agreement term. The collateral requirement amount may be adjusted annually to reflect the remaining service agreement term following the customer's timely payment of 20260HB2828PN3926 - 6 - 123456789101112131415161718192021222324252627282930

charges throughout the previous year. A large computational load customer shall provide collateral through one or more of the following forms:(i) A cash deposit.(ii) A standby irrevocable letter of credit from a financial institution.(iii) A guarantee from a parent company or corporate affiliate of the large computational load customer, if that parent or affiliate has a credit rating of at least A- from Standard & Poor's Global Ratings and A3 from Moody's Corporation, and liquidity greater than 10 times the collateral requirement.(11) Ensure that in the event of a large computational load customer's bankruptcy, insolvency, default, departure, dissolution or any other event creating an inability for the customer to pay for some or all of the tariff charges for which it is responsible, that the unrecovered costs may not be recovered from other customer classes.(12) Include interconnection queue requirements for large computational loads that include data input requirements, technical requirements and other related matters as determined by the commission.(d) Tariff filings.--Within 90 days of the effective date of this subsection, each electric distribution company or load serving entity that is serving or intends to serve a large computational load customer operating in this Commonwealth shall make a compliance filing with the commission describing the new capacity types, operational procedures and other information relevant to the service provided to large computational load customers, as determined by the commission.20260HB2828PN3926 - 7 - 123456789101112131415161718192021222324252627282930

(e) Backstop auction and IRAS implementation.--Electric generation suppliers and electric distribution companies with PJM reliability backstop auction obligations shall file and the commission shall approve procedures or tariff provisions, or both, necessary to implement the reliability backstop auction no later than June 1, 2028. Each applicable electric distribution company and transmission operator shall provide the commission with the information required under this section concurrently with the appropriate filings with the Federal Energy Regulatory Commission. The procedures or tariff provisions approved by the commission shall comply with the following:(1) Ensure that large computational load customers are charged for any PJM reliability backstop auction costs and prevent other customer classes from being charged for the costs.(2) Ensure that in the event of a large computational load customer's bankruptcy, insolvency, default, departure, dissolution or any other event creating an inability for the customer to pay for the reliability backstop auction capacity costs, that the capacity costs be reallocated to other large computational load customers. Other customer classes shall not be charged for reliability backstop auction costs if the large computational load customers are unable to pay these costs due to any of the events described under this paragraph.(3) Define reliability backstop auction capacity cost allocation, auction capacity reallocation procedure requirements, processes for reassignment of reliability backstop auction capacity in a default event and consumer protection mechanisms related to the backstop auction, as 20260HB2828PN3926 - 8 - 123456789101112131415161718192021222324252627282930

determined by the commission.(4) Establish mandatory interruptible tariffs for Interim Resource Adequacy Service eligible customers that reflect the program's guidelines for dispatch, real-time curtailment priority methods, enforcement mechanisms to ensure delivery of Interim Resource Adequacy Service megawatt obligations to PJM and other related matters as determined by the commission.(5) Pending a determination by the commission on whether Interim Resource Adequacy Service entities will or will not receive compensation for load curtailment, identify Interim Resource Adequacy Service payment amounts, consumer cost recovery mechanisms, crediting mechanisms, billing requirements and other administrative responsibilities.(f) Notification.--Each electric distribution company that is a member of PJM and is a default service provider may not provide default service to a large computational load customer unless the customer gives notice to the electric distribution company at least 180 days prior to the intended service date.Section 4. Emergency load control procedures during regional resource adequacy shortfalls.(a) Emergency load control procedures.--An electric distribution company that has received a request for interconnection from one or more large computational load customers within its service territory and is subject to the jurisdiction of the commission shall update its emergency load control procedures under 52 Pa. Code § 57.52 (relating to emergency load control and energy conservation by electric utilities) in a manner consistent with the following:(1) During a load emergency situation as defined under 20260HB2828PN3926 - 9 - 123456789101112131415161718192021222324252627282930

52 Pa. Code § 57.52(a)(1)(i), an electric distribution company shall curtail large computational load customers prior to and in lieu of any other industrial, commercial or residential customer.(2) A large computational load customer shall not be exempt from emergency curtailment standards under any circumstances.(3) Revisions to emergency load control procedures made under this section shall be filed with the commission within 60 days after the effective date of this paragraph.(b) Commission duties.--The commission shall:(1) Approve or modify an electric distribution company's update to its emergency load control procedures under this section within 120 days after submission.(2) Ensure that updates to each electric distribution company's emergency load control procedures under this section are in place prior to June 1, 2027, and will remain effective in all subsequent delivery years in which PJM projects there will be a resource adequacy shortfall expected to occur in the planning horizon that is caused primarily by the addition of large computational load customers.(3) Establish penalties for noncompliance with this section.(c) Large computational load customer reporting.--Each electric distribution company shall provide annually with the commission a listing of each large computational load customer that has submitted a request for interconnection within the company's service territory. The listing shall include all information required for the creation of a large load registry as described in PJM's tariff filing regarding Interim Resource 20260HB2828PN3926 - 10 - 123456789101112131415161718192021222324252627282930

Adequacy Service with the Federal Energy Regulatory Commission, including identifying large computational load customers that have satisfied bring your own new capacity requirements and each large computational load customer's electric demand, electric peak load and location within the electric distribution company's service territory.Section 5. Commission authority.The commission shall have general administrative authority, including the authority to interpret this act and adopt any order or regulation necessary, to implement this act.Section 6. Effective date.This act shall take effect immediately.20260HB2828PN3926 - 11 - 123456789101112

H2828B3926A04337 NAD:EJH 09/28/26 #90 A04337AMENDMENTS TO HOUSE BILL NO. 2828Sponsor: REPRESENTATIVE FIEDLERPrinter's No. 3926Amend Bill, page 11, by inserting between lines 6 and 7Section 5. Backup generation standards.(a) Disclosure.--Each large computational load customer shall disclose to the commission, the applicable electric distribution company and PJM information regarding the large computational load customer's backup generation resources or battery storage resources and the large computational load customer's capability to rely on backup generation resources or battery storage resources during a period of required load shedding or curtailment, as determined by PJM, including the amount of notice required to deploy backup generation resources or battery storage resources.(b) Emission standards.--A large computational load customer's onsite fossil-fueled backup generation shall comply with all of the following criteria:(1) Meet or exceed the Tier 4 emissions standards of the United States Environmental Protection Agency or both meet the Tier 2 emissions standards of the United States Environmental Protection Agency and be equipped with a selective catalytic reduction system or another emissions control system that more stringently reduces nitrogen oxides, where applicable.(2) Be limited to emergency use and limited testing and maintenance consistent with Federal and State air quality laws and regulations.(3) Be permitted, monitored and reported in the aggregate as a single emissions source or as part of a single emissions source, where practicable, in coordination with the Department of Environmental Protection.Amend Bill, page 11, line 7, by striking out "5" and inserting 6Amend Bill, page 11, line 11, by striking out "6" and inserting 72026/90NAD/HB2828A04337 - 1 -1234567891011121314151617181920212223242526272829303132333435